Tower 3/1 10K-31C REAR VIEW
Fig. 3-1 the rear view of the tower 3-phase series UPS
3.2 Product Specification and Performance
1) General Specification
Model
10KVA
20KVA
10K-31C
Power Rating
10KVA/9KW
20KVA/18KW
10KVA/9KW
Frequency (Hz)
50/60
Voltage
(110-276)VAC (Depends on Load Level)
Input
Current
L1/L2/L3
:
23A MAX L1/L2/L3
:
46A MAX L1/L2/L3
:
23A MAX
Voltage
288VDC
240VDC
Battery
Current
43A MAX
86A MAX
51.8A MAX
Parallel Port
(Optional)
Intelligent Slot
EPO
、
、
RS232
USB
Fan
AS400
Input Breaker
Terminal Blocks
Cover
External Battery
IEC Connector
Maintenance and Output
Switch Cover
11
Voltage
200VAC/208VAC/220VAC/230VAC/ 240VAC*
Output
Current
45A/48.1A/45.5A/4
3.5A/41.7A
90A/96.2A/90.9A/8
7.0A/83.3A
45A/48.1A/45.5A/4
3.5A/41.7A
Dimension
(WxDxH) mm
350x650x890
260*550*708
Net Weight (kg)
127
188
85
2) Electrical Performance
Input
Model
Voltage
Frequency
Power Factor
10KVA/20KVA/10K-31C Three-phase 50/60 Hz±10% >0.99(@Full load)
*
:
If
output voltage be set 200V, output power will derating to 90% of power
rating
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion
Overload capacity
Current
crest ratio
±
1%
0.9 lag
Synchronized
50/60Hz
±
10%
in Line mode
(AC mode)
±
0.1% of
normal
frequency in
Battery mode
THD<2%
Full load
(Linear
Load)/
<5% for
reference
non-linear
load
100%-110% load
transfers to Bypass
mode after 5
minutes
110%-130% load
transfers to Bypass
mode after 1
minutes
130%-150% load
transfers to Bypass
mode after 10
second
>150% load
transfers to Bypass
mode after 2 second
3:1