DETECTOR TEST
12
ADICOS HTL-2
410-2410-008 EN20
7 Detector test
WARNING!
Risk of injury due to falling deposits
Deposits on the ADICOS detectors can drop when touched during testing and
cause injury.
−
Wear appropriate protective clothing
7.1 Preparing for the Detector Test
1
Use ADICOS software to call up the detectors to be tested
2
Call up the thermal image of the detector
3
Select the tab “
Max.-Werte T”
4
In “
Zusatz-F.”
in the lower-left section, select “
Max T”
in the window
5
Press the button “
Max Löschen”
7.2
Testing HOTSPOT detectors
►
Press the heated HTL-2 with the test tube directly against
the sensor of the detector to be tested and hold it there
for several seconds.
►
Turn off HTL-2 after testing.
Use the operating switch to do so (position O)
7.3 Evaluating the detector test
Depending on the parameterization of the detector, the test is successful if an alarm is triggered
and if the “Max T” thermal image, which displays the highest temperature of every pixel, uni-
formly displays the temperature of the HTL hot plate after the test. To do this...
1
Use the ADICOS software to call up the detector to be
tested
2
Call up the thermal image of the detector
3
Select the tab “
Max.-Werte T”
4
In “
Zusatz-F.”
in the lower-left section, select “
Max T”
in
the window
5
Configure an appropriate color spread