WIRING
12
HOTSPOT-X0 Interface-X1
410-2410-011 EN12
6 Wiring
WARNING!
Installation work may only be performed, if the potentially explosive
area is released for work via a risk assessment.
−
De-energize the entire detector system and secure against
unintentional reactivation for all wiring work!
−
Wiring may only be performed by specialist personnel!
WARNING!
The ADICOS HOTSPOT-X0 Interface-X1is subject to the protection principle
and/or the ignition protection type
equipment protection by flameproof
enclosures „d“
.
−
Only use approved cable glands!
−
Firmly close enclosure lid after wiring!
6.1 Wiring of ADICOS HOTSPOT-X0 Sensor Unit
WARNING!
The connection cable must be routed according to DIN EN 60079-14!
−
Only use approved, intrinsically safe connection cables provided
by GTE!
−
Observe minimum bending radius!
1
Remove enclosure lid by rotating counter clockwise
2
Open cable gland
3
Insert sensor connection cable through cable gland
4
Connect green wire
(communication A)
to terminal 14 of
Ex barrier 1
(intrinsically safe circuit 1)
5
Connect yellow wire
(communication B)
to terminal 13 of
Ex barrier 1
(intrinsically safe circuit 1)
6
Connect brown wire
(power )
to terminal 1 of Ex
barrier 2
(intrinsically safe circuit 2)
7
Connect white wire
(power supply –)
to terminal 2 of Ex
barrier 2
(intrinsically safe circuit 2)
8
Connect shield of sensor connection cable to terminal 3 of
Ex barrier 2
(intrinsically safe circuit 2)
9
Close cable gland
10
Mount enclosure lid by rotating clockwise and pulling tight
green
yellow
white
brown