I-9106

 

Intelligent Linear Cable Heat Detector

       

 

                

Installation and Operation Manual

 

  

                                                  

      

 

 

The Intelligent Solution

 

 

 

Page 7 

should be made according to Table 1).

 

 

Table 1 

    Tray Width 

m

 

Coefficient of Multiplying Power 

        1.2 

         1.75 

         0.9 

         1.50 

        0.6 

         1.25 

        0.5 

         1.15 

        0.4 

         1.1 

When the heat cable is mounted on the power cable in sane wave type, the 

number of retaining clip can be calculated by the formula:  

The number of retaining clip

The number of half sine wave

×

2

3

) 

Mounting on the conveyer 

There are two designs.  

If the conveyer’s width is not over 3m, it can be protected by a heat cable as long 

as the conveyer. The heat cable should be fixed to the appurtenance where 

locates 2.25m over the conveyer center. The appurtenance can be a supporting 

wire or any existing fixings. The supporting wire can provide a strutting piece and 

it can be tightened by a screw every 75m. In order to prevent the heat cable falling, 

firmly clip the supporting wire and heat cable every 4m

5m with a fastener. It’s 

recommended that the supporting wire be a

φ

2 stainless steel rope, each not be 

over 150m long (galvanized steel ropes can be used as a replacement ). The 

mounting method is shown in Fig. 11.  

Retaining 
Clip

Supporting Wire

the Terminal Box

Trunbuckle 
Screw

Conveyer

Linear Cable Heat Detector

2.2

5

m

Fig. 11 Mounting of the Heat Cable

 

The heat cable can be mounted on the two sides of the conveyer. Connect the 

heat cable through heat-conductive board and roller bearing to detect over-heat 

because of bearing friction and coal powder accumulating. Please install it 

according to the field situation but do not affect operation and maintenance. 

Mounting is shown in Fig. 12.

 

HTTP://GSTRU.RU

E-MAIL: [email protected]

Summary of Contents for I-9106

Page 1: ...HTTP WWW HOMBI RU HTTP GSTRU RU E MAIL hombi hombi ru...

Page 2: ...ual The Intelligent Solution CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 2 V Mounting and Wiring 3 VI Designs and Applications 8 VII Testing...

Page 3: ...i interference techniques the detector can be used to the place where affected by the strong electromagnetic field 4 The detector can work normally when its loop is extended up to 1km The heat cable c...

Page 4: ...ure falling down 30 3 Insulated resistance 500M 4 Maximum curve radius 150mm 5 Anti voltage ability 500VAC for 1 minutes 6 Relative error Action temperature error 10 IV Structure and Operation Princip...

Page 5: ...ial In normal monitoring state the resistance of each steel wire is indefinite and the heat cable has a tiny standby current because of the terminal resistance When the ambient temperature rise up to...

Page 6: ...Z2 Z3 Z4 GWDL1 GWDL2 GWDL3 GWDL4 Fig 5 Terminals of the interface Z1 Z2 to the loops of the fire alarm control panel Z3 Z4 Transfer the loop of the fire alarm control panel GWDL1 GWDL2 to heat cable I...

Page 7: ...o be used please enwind those part which is to go through the interface to 8mm 10mm rude material belt 2 The terminal The terminal can be fixed to the cable support rack with 6 plastic expansion bolts...

Page 8: ...Mounting of the Linear Heat Cable 2 Mounting on the cable tray or support rack When the heat cable is mounted on the cable tray or support rack it should be mounted on the protection cover of monitor...

Page 9: ...re or any existing fixings The supporting wire can provide a strutting piece and it can be tightened by a screw every 75m In order to prevent the heat cable falling firmly clip the supporting wire and...

Page 10: ...ribution device resistors can be mounted by the same method See Fig 13 Dynamo Control Panel Prick Utensil Heat Cable Fig 13Mounting of the Heat Cable 5 Mounting on the Other Places The heat cable can...

Page 11: ...etector in the places where exists gunpowder blasting explosive ammunition igniters 2 Design Reference When designing select the specifications of the linear cable heat detector according to the ambie...

Page 12: ...l condition At the time the interface should not report fault or alarm 5 The detector is made up of the interface the terminal and heat cable Fig 14 shows its system composition VII Testing Instructio...

Page 13: ...e yellow Fault LED if lit there is fault on the heat cable or its testing circuit and the terminal If the Fault LED is not on press Clear on the FACP to see if the Red LED flashes when polling if the...

Page 14: ...ace and the terminal are mounted indoors fix them on the wall or metal bracket in field When mounted in open air add rain proof enclosure 3 The heat cable mustn t be curved forcedly or twisted when mo...

Page 15: ...UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email info gst uk com www gst...

Reviews: