I-9106
Intelligent Linear Cable Heat Detector
Installation and Operation Manual
The Intelligent Solution
Page 7
should be made according to Table 1).
Table 1
Tray Width
(
m
)
Coefficient of Multiplying Power
1.2
1.75
0.9
1.50
0.6
1.25
0.5
1.15
0.4
1.1
When the heat cable is mounted on the power cable in sane wave type, the
number of retaining clip can be calculated by the formula:
The number of retaining clip
=
The number of half sine wave
×
2
+
1
(
3
)
Mounting on the conveyer
There are two designs.
If the conveyer’s width is not over 3m, it can be protected by a heat cable as long
as the conveyer. The heat cable should be fixed to the appurtenance where
locates 2.25m over the conveyer center. The appurtenance can be a supporting
wire or any existing fixings. The supporting wire can provide a strutting piece and
it can be tightened by a screw every 75m. In order to prevent the heat cable falling,
firmly clip the supporting wire and heat cable every 4m
~
5m with a fastener. It’s
recommended that the supporting wire be a
φ
2 stainless steel rope, each not be
over 150m long (galvanized steel ropes can be used as a replacement ). The
mounting method is shown in Fig. 11.
Retaining
Clip
Supporting Wire
the Terminal Box
Trunbuckle
Screw
Conveyer
Linear Cable Heat Detector
2.2
5
m
Fig. 11 Mounting of the Heat Cable
The heat cable can be mounted on the two sides of the conveyer. Connect the
heat cable through heat-conductive board and roller bearing to detect over-heat
because of bearing friction and coal powder accumulating. Please install it
according to the field situation but do not affect operation and maintenance.
Mounting is shown in Fig. 12.