40s. Before testing,  3m

5m lengthened heat cable should be reserved for test. 

 

4.  Cut the cable which is put in the water and connect the terminal again, the system 

will reset to the normal monitoring state

  

5. 

Check its wiring again when an interface fails to the test, then test it once more. If it 

still fails, please return it for repair.  

VIII Troubleshooting 

Registration Fault: When registering the detector on fire alarm control panel, if 

some interfaces cannot be registered, repair according to the following steps.

 

1

) 

Read the code by hand held programmer. Check the address number, 

device type, to see whether they meet the design requirement or the code is 

repeated. If the programmer fails to read codes, so it’s certain that there are 

problems with the interface. If there is no problem with the address number and 

device type, check the loop voltage and impedance, see if there is circuit fault.

 

2

) 

For the interface with fault, please contact local office of GST or GST 

Company.  

The interface gives fault: When the FACP is in normal monitoring state, if the fault 

occurs on the interface, repair by the following steps.

 

1

) 

When the FACP is on, check the yellow Fault LED, if lit, there is fault on 

the heat cable or its testing circuit and the terminal. If the Fault LED is not on, 

press “Clear” on the FACP to see if the Red LED flashes when polling, if the Red 

LED stops flashing, there is fault on the interface.

 

2

) 

Turn off the FACP. As for the interface with fault on the heat cable and the 

terminal, check if circuit of the heat cable is open and check the resistor 

between two connection poles. If it is 10K

, it is normal; if infinite, the terminal is 

damaged.

 

3

) 

If there is not open circuit on the heat cable and the terminal after 

checking, the interface is in trouble, please return it for repair. 

 

The interface gives false alarm: When the FACP is in normal monitoring state, if the 

interface of the detector alarms falsely, repair by the following steps.

 

1

) 

Turn off the FACP: First separate the heat cable and the terminal. Check if 

their circuits are shorted separately. If the short circuit occurs to the terminal, 

check the internal components; if the short circuit occurs to the heat cable, 

please repair the heat cable. 

 

2

) 

If short circuit is found on neither heat cable nor the terminal, please 

return the interface for repair.  

IX Maintenance 

 

Measure the insulating resistor with 500VM

Ω

meter between the two-core cables every 

half year. The resistance should be over 500M

Ω

( turn off the power and disconnect the 

two ends of the heat cable when testing). If the value is below 500M

Ω

, replace the heat 

cable.

 

HTTP://GSTRU.RU

E-MAIL: [email protected]

Summary of Contents for I-9106

Page 1: ...HTTP WWW HOMBI RU HTTP GSTRU RU E MAIL hombi hombi ru...

Page 2: ...ual The Intelligent Solution CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 2 V Mounting and Wiring 3 VI Designs and Applications 8 VII Testing...

Page 3: ...i interference techniques the detector can be used to the place where affected by the strong electromagnetic field 4 The detector can work normally when its loop is extended up to 1km The heat cable c...

Page 4: ...ure falling down 30 3 Insulated resistance 500M 4 Maximum curve radius 150mm 5 Anti voltage ability 500VAC for 1 minutes 6 Relative error Action temperature error 10 IV Structure and Operation Princip...

Page 5: ...ial In normal monitoring state the resistance of each steel wire is indefinite and the heat cable has a tiny standby current because of the terminal resistance When the ambient temperature rise up to...

Page 6: ...Z2 Z3 Z4 GWDL1 GWDL2 GWDL3 GWDL4 Fig 5 Terminals of the interface Z1 Z2 to the loops of the fire alarm control panel Z3 Z4 Transfer the loop of the fire alarm control panel GWDL1 GWDL2 to heat cable I...

Page 7: ...o be used please enwind those part which is to go through the interface to 8mm 10mm rude material belt 2 The terminal The terminal can be fixed to the cable support rack with 6 plastic expansion bolts...

Page 8: ...Mounting of the Linear Heat Cable 2 Mounting on the cable tray or support rack When the heat cable is mounted on the cable tray or support rack it should be mounted on the protection cover of monitor...

Page 9: ...re or any existing fixings The supporting wire can provide a strutting piece and it can be tightened by a screw every 75m In order to prevent the heat cable falling firmly clip the supporting wire and...

Page 10: ...ribution device resistors can be mounted by the same method See Fig 13 Dynamo Control Panel Prick Utensil Heat Cable Fig 13Mounting of the Heat Cable 5 Mounting on the Other Places The heat cable can...

Page 11: ...etector in the places where exists gunpowder blasting explosive ammunition igniters 2 Design Reference When designing select the specifications of the linear cable heat detector according to the ambie...

Page 12: ...l condition At the time the interface should not report fault or alarm 5 The detector is made up of the interface the terminal and heat cable Fig 14 shows its system composition VII Testing Instructio...

Page 13: ...e yellow Fault LED if lit there is fault on the heat cable or its testing circuit and the terminal If the Fault LED is not on press Clear on the FACP to see if the Red LED flashes when polling if the...

Page 14: ...ace and the terminal are mounted indoors fix them on the wall or metal bracket in field When mounted in open air add rain proof enclosure 3 The heat cable mustn t be curved forcedly or twisted when mo...

Page 15: ...UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email info gst uk com www gst...

Reviews: