Intelligent Linear Cable Heat Detector

       

 

                

Installation and Operation Manual

 

  

                                                  

      

 

 

The Intelligent Solution

 

 

 

Page 10 

(1)  The address number of the interface should be programmed by hand held 

programmer by project’s request before it is used to the system. The interface 

is defaulted two loop, so it has two address numbers-- ×× and ×× 

+

1. If the 

address number is required to change, modify the address number of Loop I 

and that of Loop II will be added to 1 automatically. 

(2)  When there only needs one heat cable, change the device type of the interface 

from 8 to 18.  See 

Hand Held Programmer Installation and Operation Manual 

for details. 

(3)  After wiring and installation, power on the fire alarm control panel and enter 

system commission state. First check whether all the interfaces registered and 

write unregistered interface down to find faults.  As for the registered interfaces, 

they are defined as linear heat cable with device type 8 through fire alarm 

control panel. See Fire Alarm Control Panel Installation and Operation Manual 

for the specific definitions.  

(4)  All the interfaces, other detectors, modules are registered, power on the 

system and make it in normal condition. At the time, the interface should not 

report fault or alarm.  

(5)  The detector is made up of the interface, the terminal and heat cable. Fig. 14 

shows its system composition.  

VII Testing 

Instructions: After installation and commission, register the devices through the fire 

alarm control panel then check whether all the interfaces registered and write 

unregistered interface down to find faults. As for the registered interfaces, make 

simulation and manual fire test. When short condition occurs to the heat cable, the 

address number of related interface will transmit such a status to the fire alarm control 

panel which generates fire alarms. 

1.  Before testing, notify the proper authorities that the system is going to be 

maintenance and out of service temporarily. Disable the zone or system 

undergoing maintenance to avoid unwanted alarms. 

2.  Manual Fire Test: Remove the commission tool, put its 

Commission Zone 

close to 

Fire Test position on the upper part of the terminal.  Check whether the red LED is lit. 

Remove the commission tool to clear fire condition, the system goes back in normal 

monitoring state. Fig. 15 shows the fire test. 

Fire 

Test

 

Fig. 15 Fire Test  

3.  Simulation Fire Test: Put a part of curved cable into boiling water over 0.3m from 

the terminal. The cable length in the water is 1m, and fire alarm should be given in 

HTTP://GSTRU.RU

E-MAIL: [email protected]

Summary of Contents for I-9106

Page 1: ...HTTP WWW HOMBI RU HTTP GSTRU RU E MAIL hombi hombi ru...

Page 2: ...ual The Intelligent Solution CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 2 V Mounting and Wiring 3 VI Designs and Applications 8 VII Testing...

Page 3: ...i interference techniques the detector can be used to the place where affected by the strong electromagnetic field 4 The detector can work normally when its loop is extended up to 1km The heat cable c...

Page 4: ...ure falling down 30 3 Insulated resistance 500M 4 Maximum curve radius 150mm 5 Anti voltage ability 500VAC for 1 minutes 6 Relative error Action temperature error 10 IV Structure and Operation Princip...

Page 5: ...ial In normal monitoring state the resistance of each steel wire is indefinite and the heat cable has a tiny standby current because of the terminal resistance When the ambient temperature rise up to...

Page 6: ...Z2 Z3 Z4 GWDL1 GWDL2 GWDL3 GWDL4 Fig 5 Terminals of the interface Z1 Z2 to the loops of the fire alarm control panel Z3 Z4 Transfer the loop of the fire alarm control panel GWDL1 GWDL2 to heat cable I...

Page 7: ...o be used please enwind those part which is to go through the interface to 8mm 10mm rude material belt 2 The terminal The terminal can be fixed to the cable support rack with 6 plastic expansion bolts...

Page 8: ...Mounting of the Linear Heat Cable 2 Mounting on the cable tray or support rack When the heat cable is mounted on the cable tray or support rack it should be mounted on the protection cover of monitor...

Page 9: ...re or any existing fixings The supporting wire can provide a strutting piece and it can be tightened by a screw every 75m In order to prevent the heat cable falling firmly clip the supporting wire and...

Page 10: ...ribution device resistors can be mounted by the same method See Fig 13 Dynamo Control Panel Prick Utensil Heat Cable Fig 13Mounting of the Heat Cable 5 Mounting on the Other Places The heat cable can...

Page 11: ...etector in the places where exists gunpowder blasting explosive ammunition igniters 2 Design Reference When designing select the specifications of the linear cable heat detector according to the ambie...

Page 12: ...l condition At the time the interface should not report fault or alarm 5 The detector is made up of the interface the terminal and heat cable Fig 14 shows its system composition VII Testing Instructio...

Page 13: ...e yellow Fault LED if lit there is fault on the heat cable or its testing circuit and the terminal If the Fault LED is not on press Clear on the FACP to see if the Red LED flashes when polling if the...

Page 14: ...ace and the terminal are mounted indoors fix them on the wall or metal bracket in field When mounted in open air add rain proof enclosure 3 The heat cable mustn t be curved forcedly or twisted when mo...

Page 15: ...UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email info gst uk com www gst...

Reviews: