GSM SMS Alarm Messenger
Pro X (Premium)
33
Example:
A1M:0.600,1.000,1,0.500,0.100
0.600
AD value range 0.600
1.000
Start Value is “1.000”
(4mA * 250
Ω
=1)
1
Alarm
Enabled
0.500
Threshold
High
0.100
Threshold
Low
Standard range of data captured in AD Channel 1 is 4~20mA.
AI1 value depends on user setting of “Range”, “Start Value” and the input current “c”.
Start Value = 4mA x 250
Ω
= 1
AD Range
= usually specified by the current type transducer
(c x 250 – Start Value)
AI1 =
------------------------------- x Range
(0.02 x 250 – Start Value)
AI1 reported value will be = Range x (0.012 x 250 – Start Value) / (5 – Start Value)
When current input is 12mA, AI1 = 0.6 x (0.012 x 250 – 1) / (5 – 1) = 0.3
When user requires:
High level alarm at 0.018mA
Low level alarm at 0.008mA
H = (0.018 x 250 – 1) x 0.6 / (0.02 x 250 – 1) = 0.525
L = (0.008 x 250 – 1) x 0.6 / (0.02 x 250 – 1) = 0.15
When AI1 value is over 0.525 or below 0.150, alarm will be triggered – SMS alert
message will be sent out to phone number 1 and relay 1 is turned on.
Command: PWD:1234,ADVALE1:0.600,1.000,1,0.525,0.150%
Command: PWD:1234,ADCOUT1:10,1000,100%