THEORY OF OPERATION
Top Dry Autoflow Theory of Operation
Control Panel Switches Status:
Control Power:
On
24v Power:
On
Moisture Control Thermostat:
On
Aeration Fan:
Auto
Load Auger:
Auto
Fan:
Auto
Heater:
Auto
Dump:
Auto
Dry & Hold:
Off
Emergency Stop Switches Status
Autoflow Control Box Emergency Stop: pulled out
Fill System Control Box Emergency Stop: pulled out
Actuator Control Box Emergency Stop: pulled out
Aeration Fan Bypass:
Continuos
When the Top Dry is in a ready state; that
is, with no grain the
Drying Chamber
and wet
grain in the
Wet Storage Tank, Fill System #1
and
Fill System #2
will start to fill the
Drying Chamber
with wet grain when the start switch is pressed on
the
Dryer Control Panel.
In single fill system
units on
Fill System #1
will start. When grain
reaches the
Drying Chamber Low Level Rotary
Switch
the
Aeration Fan
, and the
Master Drying
Fan
will come on, and the
Fan Delay
will start to
count down. When the
Fan Delay
reaches zero the
Slave Drying Fan
will start, the
Airswitch
will
close, and the
Dry Timer
will start to count down.
In single fan units the
Fan Delay
will not count
down and the
Airswitch
will close after the
Master
Drying Fan
starts. After a twenty second
Purge
Delay
the fan/heater unit(s) will ignite. When the
Plenum Temperature
reaches the
Cycle Setpoint
on
the
Hi-Lo Thermostat
the fan/heater unit(s) will
cycle to
Low-Fire
. When the
Plenum Temperature
falls ten degrees below the
Cycle Setpoint
the fan/
heater unit(s) will cycle back to
High-Fire.
The
fan/heater unit(s) will continue to cycle throughout
the drying.
When grain reaches the
Chamber High
Level Rotary Switch
the
Load Delay
will begin to
count down. When the
Load Delay
reaches zero
Fill System #2
will shut off and the
Aux. 1 Delay
will begin to count down. When the
Aux. 1 Delay
reaches zero
Fill System #1
will shut off.
If the
Chamber High Level Rotary Switch
becomes exposed due to shrinkage of grain in the
Drying Chamber
, the fill system(s) will start and
refill the
Drying Chamber
. When grain reaches
the
Chamber High Level Rotary Switch
the fill
system(s) will shut off after the delays.
When the
Dry Timer
reaches zero and the
Grain Temperature Setpoint
on the
Moisture
Control Thermostat
has not been reached the unit
will go into
Temperature Hold.
When the grain
temperature reaches the
Grain Temperature
Setpoint
on the
Moisture Control Thermostat
the
unit will continue to the
Dump Cycle
. In the
Dump Cycle
the
Linear Actuator
in the
Actuator
Control Box
extends, the dump chutes lower, and
grain is dumped from the
Drying Chamber
into
Storage Chamber
. Immediately after the dump
chutes open the
Unload Timer
begins to count
down. When the
Unload Timer
reaches zero the
dump chutes raise and grain stops dumping from
the
Drying Chamber
into the
Storage Chamber.
During the
Dump Cycle
, 1/3 of the grain is
dumped into the
Storage Chamber.
Summary of Contents for PNEG-728
Page 1: ...1 Autoflow Operation 1 Autoflow Operation PNEG 728 ...
Page 2: ...Autoflow Operation 2 This page was left blank intentionally ...
Page 6: ...Autoflow Operation 6 DECAL PLACEMENT ...
Page 10: ...Autoflow Operation 10 CONTROL SYSTEM Electronic Monitoring Control System ...
Page 13: ...13 Autoflow Operation CONTROL PANEL ...
Page 14: ...Autoflow Operation 14 CONTROL SYSTEM Electronic Monitoring Control System ...
Page 19: ...19 Autoflow Operation CONTROL SYSTEM ...
Page 20: ...Autoflow Operation 20 CONTROL SYSTEM ...
Page 21: ...21 Autoflow Operation CONTROL SYSTEM ...
Page 22: ...Autoflow Operation 22 CONTROL SYSTEM ...
Page 28: ...Autoflow Operation 28 FILL SYSTEM CONTROL BOX ...