P1
Burner ignition power % with LPG supply 0
99
40
P2
Burner maximum power %
0
99
99
P3
"Post circulation" time sec
0
99
60
P4
"Post ventilation" time sec
0
99
10
P5
Anti frequent ignition parameter min
0
255
0
P6
Service function
0 = deactivated 1= minimum power 2= maximum power
P7
High temperature climate curve
parameter
-20
10
0
P9
Type of system pressure measurement
device
0= none
1= 0.5-2.5 V transducer (B type)
2= 0.5-3.5 V transducer (A type)
3= pressure switch 4= flow switch
P10
ALL PARAMETER MODIFICATION ENABLE
CODE
0-99
5 sec
N° PAGINA
VALORE
Pic. 38
Pic. 39
THE DESCRIPTIONS AND VALUES GIVEN IN ITALICS IN THE TABLE BELOW ARE ONLY
TO BE USED WHEN IT IS NECESSARY TO CHECK THE CONFIGURATION.
MODIFICATION OF THE PARAMETERS IN ITALICS CAN CAUSE THE BOILER TO
MALFUNCTION AND BE DAMAGED OR DESTROYED.
INSTALLER MENU
Value
Page number