24
DIAPHRAGMS
COAXIAL SYSTEM
Diaphragm diameter
BETWEEN
AND
Ivy 24 MR
Ivy 28 MR
Ivy 32 MR
0.5 metri
1 metri
35 mm
37 mm
39 mm
>1 metri
2 metri
37 mm
39 mm
41 mm
>2 metri
3 metri
37 mm
39 mm
41 mm
>3 metri
4 metri
39 mm
41 mm
44 mm
>4 metri
5 metri
41 mm
44 mm
-
SPLIT SYSTEM diaphragm diameter
Ivy 24 MR
Ivy 28 MR
Ivy 32 MR
>70 <100 Pascal
Ø 35 mm
>92 <110 Pascal
Ø 37 mm
>107 Pascal
Ø 35 mm
>100 <120 Pascal
Ø 37 mm
>110 <150 Pascal
Ø 39 mm
>107 <145 Pascal
Ø 44 mm
>120 <190 Pascal
Ø 39 mm
>150 <175 Pascal
-
≥145 Pascal
-
-
-
ALWAYS CONNECT A MINIMUM FLUE EVACUATION AND INTAKE SECTION FOR BOTH
SYSTEMS OF AT LEAST 0.5 METRES (COAXIAL PIPE = 0.5m + 90° ELBOW; SPLIT 0.25 m
FLUE EVAC 0.25 m RESPECTIVE 90° ELBOWS)
FOLLOW APPLICABLE LEGISLATION AND REGULATIONS TO THE LETTER
INSTALL AIR INTAKE AND FLUE EVACUATION SYSTEMS CONFORMING TO THE
SPECIFICATIONS GIVEN ON THE TECHNICAL DATA PLATE AND OBSERVE ANY
LIMITATIONS ARISING FROM APPLICABLE LEGISLATION AND REGULATIONS TO THE
LETTER.
ONLY USE APPROVED COMPONENTS FOR AIR INTAKE AND COMBUSTION GAS
EVACUATION SYSTEMS WHICH ARE OF THE CORRECT DIMENSIONS AND PURPOSELY
DESIGNED AND MANUFACTURED FOR THE PURPOSE.
FOLLOW INSTALLATION INSTRUCTIONS TO THE LETTER.
INSULATE ANY FLUE SECTIONS WHICH WILL BE EXPOSED TO LOW TEMPERATURES.
TAKE MEASURES TO AVOID THE FORMATION OF EXCESSIVE CONDENSATION. ENSURE
THAT ANY CONDENSATION DOES NOT EVEN MINIMALLY AFFECT ANY INTERNAL
PART OF THE BOILER.
WHENEVER NECESSARY, PLACE APPROPRIATE CONDENSATE TRAPS ON THE FLUE
EVACUATION LINE:
Ensure the following before commissioning the boiler:
• THAT THE FLUE EVACUATION AND AIR INTAKE LINES ARE PERFECTLY SEALED
• THAT THEY ARE CORRECTLY POSITIONED AND FASTENED
• THAT THERE ARE NO MECHANICAL, THERMAL OR CHEMICAL STRESSES ON THE
LINES WHICH COULD EVEN MOMENTARILY COMPROMISE THEIR INTEGRITY.
INSTALL SYSTEMS TO ABSORB ANY THERMAL EXPANSION WHEN THE SECTIONS OF
FLUE DUCTING ARE LONGER THAN THE MINIMUM SPECIFIED LENGTHS.
AIR INTAKE AND COMBUSTION GAS EVACUATION SYSTEM: IMPORTANT INFORMATION