The charts below show possible control modes of TPE
Series 1000 pumps in different applications.
Control options
Communication with TPE Series 1000 pumps is
possible via:
• a central building management system
• a remote control (Grundfos R100)
• a control panel.
The purpose of controlling a TPE Series 1000 pumps
is to monitor and control the pressure, temperature,
flow and liquid level of the system.
For further information on control options of TPE
pumps, see page 20.
Control mode
Application
Constant curve
Single-pipe heating systems.
Systems with three-way valves.
Heating and cooling surfaces.
Chiller pumps.
Constant differential pressure
Systems with two-way valves.
(Sensor is needed)
Temperature control
Single-pipe heating systems.
Systems with three-way valves.
Cooling towers.
Chiller pumps.
Domestic hot water recirculation systems.
(Sensor is needed)
Constant flow
Heating and cooling surfaces.
Cooling towers.
Flow filters.
(Sensor is needed)
Proportional differential pressure (measured)
System with two-way valves.
(Differential pressure sensor is located in
the system)
(Sensor is needed)