Grundfos submersible motors, 60 Hz
Hp
Ph
Volt
[V]
SF
Circuit breaker or fuses
Amperage
Full load
Max. thrust
[lbs]
Std.
Delay
Start
[A]
Max.
[A]
Eff.
[%]
Power factor
6-inch, three-phase motors
7.5
3
208-230
1.15
65
40
114-130
23.4 - 27.5
81
85-84
6070
7.5
3
460
1.15
30
17
68
13.2
81
85
6070
7.5
3
575
1.15
30
17
51
10.2
81
85
6070
10
3
208-230
1.15
90
50
126-142
30.0 - 37.5
82
86-84
6070
10
3
460
1.15
40
25
75
17.4
82
85
6070
10
3
575
1.15
40
25
56.5
13.4
82
85
6070
15
3
208-230
1.15
130
75
198-224
44.5 - 53.5
83
86-84
6070
15
3
460
1.15
60
35
112
25
83
84
6070
15
3
575
1.15
60
35
84
19.4
83
84
6070
20
3
208-230
1.15
175
100
310-350
57.5 - 71.5
84
86-84
6070
20
3
460
1.15
80
45
186
33.5
84
84
6070
20
3
575
1.15
80
45
144
26
84
84
6070
25
3
208-230
1.15
200
125
395-445
71-87
84
87-84
6070
25
3
460
1.15
100
60
236
41
84
84
6070
25
3
575
1.15
100
60
180
32
84
84
6070
30
3
208-230
1.15
250
150
445-500
81-104
84
87-84
6070
30
3
460
1.15
125
70
265
48
85
85
6070
30
3
575
1.15
125
70
194
37
85
85
6070
40
3
460
1.15
170
90
330
65
85
84
6070
40
3
575
1.15
170
90
250
49.5
85
84
6070
50
3
460
1.15
225
125
405
73.0
83
83
6182
8-inch, three-phase motors
40
3
460
1.15
175
100
380
55.7
83
85
13000
50
3
460
1.15
225
125
550
67.8
84
85
13000
60
3
460
1.15
250
150
640
80.4
86
85
13000
75
3
460
1.15
300
175
580
97.4
86
86
13000
100
3
460
1.15
400
225
570
130.4
87
86
13000
125
3
460
1.15
500
300
600
160.0
87
87
13000
150
3
460
1.15
600
350
580
191.3
86
87
13000
10-inch, three-phase motors
175
3
460
1.15
700
400
570
230.4
88
85
13000
200
3
460
1.15
800
500
620
265.2
87
82
13000
250
3
460
1.15
1100
600
610
352.2
87
79
13000
40
English (US)