6.7.6 Control box or panel grounding
DANGER
Electric shock
Death or serious personal injury
‐
The control box or control panel must be permanently
grounded in accordance with the National Electrical
Code/Canadian Electrical Code and local codes or
regulations.
The ground wire must be a bare copper conductor at least the same
size as the submersible drop cable wire size.
Run the ground wire as short a distance as possible and fasten it
securely to a true grounding point.
True grounding points are considered to be one of the following:
•
a grounding rod driven into the water strata
•
a steel well casing submerged into the water lower than the
pump installation depth
•
steel outlet pipes without insulating couplings.
If plastic outlet pipe and well casing are used or if a grounding wire
is required by local codes, connect a properly sized, bare copper
wire to a stud on the motor and run to the control panel.
DANGER
Explosive environment
Death or serious personal injury
‐
Do not ground to a gas supply line. Connect the
grounding wire to the ground point first and then to the
terminal in the control box or control panel.
1
2
3
4
5
6
12
13
14
7
8
9
10
11
TM065266
Wiring and installation diagram
Pos.
Description
1
Power supply
2
Electrical disconnect box
3
Control box
4
House supply
5
Conduit connector
6
Submersible drop cable
7
Pressure gauge
8
Pressure switch
9
Pressure tank
10
Well seal
11
Tape
12
Pump
13
Motor
14
Conduit *
*
Conduit for proper support and protection of the cable against damage
between the motor and the point of supply connection.
19
English (US)