background image

Gru

ndf
os
 c

o

mp
an

ie

s

Argentina

Bombas GRUNDFOS de Argentina S.A.
Ruta Panamericana km. 37.500 Centro 
Industrial Garin
1619 - Garin Pcia. de B.A.
Phone: +54-3327 414 444
Telefax: +54-3327 45 3190

Australia

GRUNDFOS Pumps Pty. Ltd. 
P.O. Box 2040 
Regency Park 
South Australia 5942 
Phone: +61-8-8461-4611 
Telefax: +61-8-8340 0155 

Austria

GRUNDFOS Pumpen Vertrieb 
Ges.m.b.H.
Grundfosstraße 2 
A-5082 Grödig/Salzburg 
Tel.: +43-6246-883-0 
Telefax: +43-6246-883-30 

Belgium

N.V. GRUNDFOS Bellux S.A. 
Boomsesteenweg 81-83 
B-2630 Aartselaar 
Tél.: +32-3-870 7300 
Télécopie: +32-3-870 7301

Belarus

Представительство

 

ГРУНДФОС

 

в

 

Минске

220125, 

Минск

ул

Шафарнянская

, 11, 

оф

. 56, 

БЦ

 

«

Порт

»

Тел

.: +7 (375 17) 286 39 72/73

Факс

: +7 (375 17) 286 39 71

E-mail: [email protected]

Bosnia and Herzegovina

GRUNDFOS Sarajevo
Zmaja od Bosne 7-7A,
BH-71000 Sarajevo
Phone: +387 33 592 480
Telefax: +387 33 590 465
www.ba.grundfos.com
e-mail: [email protected]

Brazil

BOMBAS GRUNDFOS DO BRASIL
Av. Humberto de Alencar Castelo 
Branco, 630
CEP 09850 - 300
São Bernardo do Campo - SP
Phone: +55-11 4393 5533
Telefax: +55-11 4343 5015

Bulgaria

Grundfos Bulgaria EOOD
Slatina District
Iztochna Tangenta street no. 100
BG - 1592 Sofia
Tel. +359 2 49 22 200
Fax. +359 2 49 22 201
email: [email protected]

Canada

GRUNDFOS Canada Inc. 
2941 Brighton Road 
Oakville, Ontario 
L6H 6C9 
Phone: +1-905 829 9533 
Telefax: +1-905 829 9512 

China

Grundfos Alldos
Dosing & Disinfection

ALLDOS (Shanghai) Water Technology 
Co. Ltd.
West Unit, 1 Floor, No. 2 Building (T 4-2)
278 Jinhu Road, Jin Qiao Export 
Processing Zone
Pudong New Area 
Shanghai, 201206
Phone: +86 21 5055 1012
Telefax: +86 21 5032 0596
E-mail: 
[email protected] 

China

GRUNDFOS Pumps (Shanghai) Co. Ltd.
10F The Hub, No. 33 Suhong Road
Minhang District
Shanghai 201106
PRC
Phone: +86-21 6122 5222 
Telefax: +86-21 6122 5333

COLOMBIA

GRUNDFOS Colombia S.A.S.
Km 1.5 vía Siberia-Cota Conj. Potrero 
Chico,
Parque Empresarial Arcos de Cota Bod. 
1A.
Cota, Cundinamarca
Phone: +57(1)-2913444
Telefax: +57(1)-8764586

Croatia

GRUNDFOS CROATIA d.o.o.
Buzinski prilaz 38, Buzin
HR-10010 Zagreb
Phone: +385 1 6595 400 
Telefax: +385 1 6595 499
www.hr.grundfos.com

GRUNDFOS Sales Czechia and 
Slovakia s.r.o.

Č

apkovského 21

779 00 Olomouc
Phone: +420-585-716 111

Denmark

GRUNDFOS DK A/S 
Martin Bachs Vej 3 
DK-8850  Bjerringbro 
Tlf.: +45-87 50 50 50 
Telefax: +45-87 50 51 51 
E-mail: [email protected]
www.grundfos.com/DK

Estonia

GRUNDFOS Pumps Eesti OÜ
Peterburi tee 92G
11415 Tallinn
Tel: + 372 606 1690
Fax: + 372 606 1691

Finland

OY GRUNDFOS Pumput AB 
Trukkikuja 1
FI-01360 Vantaa   
Phone: +358-(0)207 889 500

France

Pompes GRUNDFOS Distribution S.A. 
Parc d’Activités de Chesnes 
57, rue de Malacombe 
F-38290 St. Quentin Fallavier (Lyon) 
Tél.: +33-4 74 82 15 15 
Télécopie: +33-4 74 94 10 51 

Germany

GRUNDFOS Water Treatment GmbH
Reetzstraße 85
D-76327 Pfinztal (Söllingen)
Tel.: +49 7240 61-0 
Telefax: +49 7240 61-177
E-mail: [email protected] 

Germany

GRUNDFOS GMBH
Schlüterstr. 33
40699 Erkrath
Tel.: +49-(0) 211 929 69-0 
Telefax: +49-(0) 211 929 69-3799
E-mail: [email protected]
Service in Deutschland:
E-mail: [email protected]

Greece

GRUNDFOS Hellas A.E.B.E. 
20th km. Athinon-Markopoulou Av. 
P.O. Box 71 
GR-19002 Peania 
Phone: +0030-210-66 83 400 
Telefax: +0030-210-66 46 273

Hong Kong

GRUNDFOS Pumps (Hong Kong) Ltd. 
Unit 1, Ground floor 
Siu Wai Industrial Centre 
29-33 Wing Hong Street & 
68 King Lam Street, Cheung Sha Wan 
Kowloon 
Phone: +852-27861706 / 27861741 
Telefax: +852-27858664 

Hungary

GRUNDFOS Hungária Kft.
Tópark u. 8
H-2045 Törökbálint, 
Phone: +36-23 511 110
Telefax: +36-23 511 111

India

GRUNDFOS Pumps India Private 
Limited
118 Old Mahabalipuram Road
Thoraipakkam
Chennai 600 097
Phone: +91-44 4596 6800

Indonesia

PT. GRUNDFOS POMPA
Graha Intirub Lt. 2 & 3
Jln. Cililitan Besar No.454. Makasar, 
Jakarta Timur
ID-Jakarta 13650
Phone: +62 21-469-51900
Telefax: +62 21-460 6910 / 460 6901

Ireland

GRUNDFOS (Ireland) Ltd. 
Unit A, Merrywell Business Park
Ballymount Road Lower
Dublin 12 
Phone: +353-1-4089 800 
Telefax: +353-1-4089 830 

Italy

GRUNDFOS Pompe Italia S.r.l. 
Via Gran Sasso 4
I-20060 Truccazzano (Milano)
Tel.: +39-02-95838112 
Telefax: +39-02-95309290 / 95838461 

Summary of Contents for SMART Digital XL DDA 120-7

Page 1: ...SMART Digital XL DDA From 60 to 200 l h Installation and operating instructions GRUNDFOS INSTRUCTIONS Further languages http net grundfos com qr i 98767821...

Page 2: ...gation 22 7 2 2 Operating states 22 7 2 3 Sleep mode energy saving mode 22 7 2 4 Overview of display symbols 23 7 3 Main menus 24 7 3 1 Operation 24 7 3 2 Info 24 7 3 3 Alarm 24 7 3 4 Setup 25 7 4 Ope...

Page 3: ...be observed Information attached to the pump must be observed Leakages of dangerous substances must be disposed of in a way that is not harmful to humans animals and the environment Damage caused by e...

Page 4: ...6 Diaphragm leakage To avoid any danger resulting from diaphragm leakage observe the following Perform regular maintenance See section 8 1 Regular maintenance Never operate the pump with blocked or so...

Page 5: ...4 Technical data Dimensions The storage location must be protected from rain humidity condensation direct sunlight and dust The product must be drained completely The product must be cleaned 2 2 Unpac...

Page 6: ...ion Areas of application Drinking water treatment Wastewater treatment Boiler water treatment Cooling water treatment Process water treatment CIP Clean In Place Observe section 4 2 Technical data for...

Page 7: ...power supply The device complies with electrical safety class I TM06 7046 3418 Pos Description Pos Description 1 Type designation 6 Enclosure class 2 Voltage 7 Marks of approval 3 Frequency 8 Country...

Page 8: ...3FG C Ceramics SS Stainless steel 1 4401 Control cube DDA 60 10 FCM PVC V C F 31U3U3FG F Front mounted change to left or right is possible Supply voltage DDA 60 10 FCM PVC V C F 31U3U3FG 3 100 240 V 5...

Page 9: ...heel 7 1 4 100 key 7 1 5 Signal inputs outputs 5 3 6 Mounting plate 7 Mains connection 8 Start stop key 7 1 9 Dosing head 10 Valve outlet side 11 Deaeration valve 12 Connection deaeration hose 13 Pres...

Page 10: ...ing with wet valves2 m 1 5 Min pressure difference between inlet and outlet side bar 16 psi 14 56 Max inlet pressure inlet side bar 2 psi 29 Max viscosity in SlowMode 25 with spring loaded valves3 mPa...

Page 11: ...ety class I Pollution degree 2 Signal input Max load for level input 12 V 5 mA Max load for pulse input 12 V 5 mA Max load for External stop input 12 V 5 mA Min pulse length ms 5 Max pulse frequency H...

Page 12: ...inless steel C 120 The dosing head material Polyvinyl chloride PVC must not be used in CIP applications TM06 7049 3818 C B 283 5 G5 4 A1 A2 D A 140 5 25 194 183 5 4 x 7 4 x 9 187 159 140 29 36 172 5 1...

Page 13: ...e pump on the mounting plate 1 Remove the locking screws from their transport position on the mounting plate 2 Place the pump on the mounting plate support clamps and slide it in as far as possible Th...

Page 14: ...ift and line diameter see section 4 1 Technical data Shorten hoses and pipes at right angles Ensure that there are no loops or kinks in the hoses Keep inlet line as short as possible Route inlet line...

Page 15: ...collecting tray Fig 8 Hydraulic connection Pipe connection type U3U3 For details on connection types see section 3 5 Type key 1 Make sure the system is pressureless 2 Push union nut 2 across pipe 3 3...

Page 16: ...llecting tray Fig 10 Hydraulic connection type A7A7 Fig 11 Hydraulic connection type A1A1 A3A3 5 3 Electrical connection The mains plug is the separator separating the pump from the mains All electric...

Page 17: ...nsulation TM06 7054 3818 2 1 3 4 4 4 5 3 2 2 1 2 3 4 1 2 1 3 2 1 GND GND GND 1 2 3 4 1 2 3 4 1 2 5 3 4 3 4 1 2 1 2 5 3 4 4 5 3 1 GND BUS BUS Symbol Function Pin assignment 1 brown 2 white 3 blue 4 bla...

Page 18: ...e power supply 3 Proceed according to sections 6 3 Setting the menu language 6 4 Deaerating the pump 6 5 Calibrating the pump TM06 7060 3716 TM06 7256 3716 CAUTION Chemical hazard Minor or moderate pe...

Page 19: ...e 6 Press the click wheel to select the highlighted language 7 Press the click wheel again to confirm the Confirm settings prompt and apply the setting Fig 15 Set menu language Operation English Manua...

Page 20: ...re is deviating or fluctuating backpressure as long as the AutoFlowAdapt function has been enabled See section 7 11 AutoFlowAdapt Requirements The hydraulics and electrics of the pump are connected Se...

Page 21: ...e pump executes 200 dosing strokes and displays the factory calibration value e g 1 05 l 6 Remove the inlet line from the measuring beaker and check the remaining volume V2 e g 1 39 l 7 From V1 and V2...

Page 22: ...in 7 2 2 Operating states The operating state of the pump is indicated by a symbol and display colour For some alarms the pump tries to restart periodically Observe section 9 Faults 7 2 3 Sleep mode e...

Page 23: ...4 4 Timer Sect 7 4 5 7 4 6 Running Standby Stop Deaerating Diaphragm position out Sect 8 Additional display Sect 7 15 2 AR variant Target flow FCM variant Actual flow Remaining batch volume Batch Tim...

Page 24: ...he pump to start Up to 10 warnings and alarms together with their date time and cause are listed in chronological order If the list is full the oldest entry will be overwritten see section 9 Faults TM...

Page 25: ...Operation menu The pump automatically switches between the units Alternatively the display can be reset to US units gph See section 7 15 Display setup Fig 18 Manual mode The setting range depends on t...

Page 26: ...ed for subsequent processing The contents of the memory will be deleted by Switching off the power supply Changing the operation mode Interruption e g alarm External stop 7 4 3 Analog 0 4 20 mA In thi...

Page 27: ...is described by a line that passes through Q 0 l h between 2 mA and 16 mA it drops proportionally from 60 l h to 18 l h and from 16 mA onwards it passes through Q2 18 l h Set analog scaling in the Ope...

Page 28: ...uption e g interruption of the mains voltage External stop the dosing will be stopped while the time continues running After suspending the interruption the pump will continue to dose according to the...

Page 29: ...cording to the actual timeline position The following settings are required in the Setup Dosing timer week menu for each dosing procedure Fig 32 Setting the timer The batch volume e g 986 ml is set in...

Page 30: ...the suction stroke can be reduced to 50 or 25 Fig 35 SlowMode menu TM06 7094 2916 Setting Description of output signal Variant FCM AR Output Input Analog feedback signal not for master slave applicat...

Page 31: ...movement after the alarm was acknowledged by the user Functions which require the reference movement are deactivated until the reference movement was performed These functions are Auto deaeration Flow...

Page 32: ...n stroke length Causes for deviations can be identified immediately by aligning the current indicator diagram with a calculated optimum indicator diagram Air bubbles in the dosing head reduce e g the...

Page 33: ...ibration of pressure sensor The pressure sensor is calibrated in the factory As a rule it does not need to be re calibrated If specific circumstances e g pressure sensor exchange extreme air pressure...

Page 34: ...ring pressure fluctuations are identified See section 7 9 Pressure monitoring Flow measurement deviations from the target flow are identified See section 7 10 Flow measurement Example of AutoFlowAdapt...

Page 35: ...d 7 15 2 Additional display The additional display provides additional information about the current pump status The value is shown in the display with the corresponding symbol In Manual mode the Actu...

Page 36: ...Ethernet For internal communication between the CIU and the dosing pump GENIbus is used 7 17 3 Activate communication 1 Set the pump to operating state Stop with the Start stop key 2 Switch off the po...

Page 37: ...Deactivate communication After deactivating the bus control function the pump can start automatically Bus control function can be deactivated in the Setup Bus menu After deactivation all submenus in...

Page 38: ...functions Relay 2 are stopped Timer dosing and timer relay output functions must be restarted manually Changing time or date can cause increase or decrease in concentration In Output Relay 1 Relay 2...

Page 39: ...ls as follows Both signal inputs are allocated to the normally open contact NO in the factory They can be re allocated in the Setup Inputs Outputs menu to normally closed contact NC 7 19 Basic setting...

Page 40: ...ct selection grundfos com When the Service now message appears displayed daily the pump must be serviced immediately The symbol appears in the Operation menu The order number of the service kit requir...

Page 41: ...Minor or moderate personal injury Observe the material safety data sheet of the dosing medium Wear protective clothing gloves and goggles when working on the dosing head connections or lines Collect...

Page 42: ...on screw 1a 1e O ring 1b Valve ball 1c Valve housing 1d Groove for O ring 1f 1h Flat gasket 1g Hose nipple 2 Flange 2a 2d O ring 2b Screws 2c Intermediate ring 3 Diaphragm 4 Valve on outlet side 5 Dos...

Page 43: ...at dosing liquid has entered the pump housing Otherwise proceed as described in section 8 6 2 Dosing liquid in the pump housing This section refers to fig 44 45 1 DDA 60 10 Place new O rings 2a 2d in...

Page 44: ...the pump 20 Observe the notes on commissioning in section 6 Startup 8 4 5 Replacing the DLD sensor This section refers to fig 44 45 1 Put on the stipulated personal protective equipment 2 Switch off...

Page 45: ...nnect FlowControl or DLD signal connection if present See fig 13 14 8 For plastic dosing head Remove screws 6 Remove dosing head 5 together with cover plate 6a 9 For stainless steel dosing head Remove...

Page 46: ...ion The last 10 faults are stored in the Alarm main menu When a new fault occurs the oldest fault is deleted The two most recent faults are shown in the display you can scroll through all the other fa...

Page 47: ...stall additional spring loaded valve approx 2 bar on the outlet side to increase the pressure differential Deaeration valve open Close the deaeration valve Air bubble Warning Broken leaky inlet line C...

Page 48: ...g 13 Check plug connection Replace dosing head with sensor if necessary If the Flow control connection at the pump is damaged send the pump for repair See section 8 7 Repairs Motor blocked Alarm Backp...

Page 49: ...rve section 4 1 Technical data Cavitation Alarm Blocked constricted squeezed inlet line Blocked constricted inlet valve Suction lift too high Viscosity too high Cavitation moves the motor Enable SlowM...

Page 50: ...lean inlet line install strainer Suction lift too high Reduce suction lift Install priming aid Enable SlowMode See section 7 6 SlowMode Viscosity too high Enable SlowMode See section 7 6 SlowMode Use...

Page 51: ...in brief We hereby declare that the pump has been cleaned and is completely free from chemical biological and radioactive substances _____________________________________ Date and signature __________...

Page 52: ...GRUNDFOS CROATIA d o o Buzinski prilaz 38 Buzin HR 10010 Zagreb Phone 385 1 6595 400 Telefax 385 1 6595 499 www hr grundfos com GRUNDFOS Sales Czechia and Slovakia s r o apkovsk ho 21 779 00 Olomouc P...

Page 53: ...b 11070 Novi Beograd Phone 381 11 2258 740 Telefax 381 11 2281 769 www rs grundfos com Singapore GRUNDFOS Singapore Pte Ltd 25 Jalan Tukang Singapore 619264 Phone 65 6681 9688 Telefax 65 6681 9689 Slo...

Page 54: ...835 Trademarks displayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2019 G...

Reviews: