3.3 SM 111 mounted on a DIN rail

If the SM 111 is to be mounted on a DIN rail, a kit No 
96692709 must be fitted on the back of the SM 111. 
See page 76.

3.4 SM 111 mounted in the pump

1. See the configuration letter on the pump 

nameplate.

2. Set the DIP switch (pos. 11) of the IO 111. 

See the installation and operating instructions of 
the IO 111.

3. Connect the pump to the IO 111. See the wiring 

diagram on page 75.

3.5 SM 111 mounted in a control panel

1. See the wiring diagram of the pump.

2. Connect the sensors as described in section 

3.6 Connection of sensors.

3. Set the DIP switch (pos. 11) of the IO 111 to 

configuration B. See the installation and 
operating instructions of the IO 111.

3.6 Connection of sensors

Fig. 3

Connection pins

See diagram at the end of this booklet.

4. Start-up

Start-up must carried out by authorized personnel. 
Switch on the power supply and check that the 
indication on the IO 111 is as expected. If the signal 
is OK, the system is ready for operation.
If not, check that

the SM 111 is connected correctly to the IO 111 
(see the installation and operating instructions of 
the IO 111).

all sensors are connected correctly.

First time voltage is applied, the SM 111 will read all 
inputs to detect which sensors are connected. If a 
valid signal is measured, the SM 111 will register that 
a sensor is present and save the status.

If the IO 111 indicates a sensor error or configuration 
error, the sensor detection must be changed.

1. Change DIP switch no. 9 on the IO 111 from OFF 

to ON. See fig. 4. After approx. 5 seconds, the 
SM 111 will reset, and the sensor detection is 
completed. 

2. Set the DIP switch to OFF.

Fig. 4

DIP switches on the IO 111

5. Maintenance

The SM 111 requires no maintenance.

6. Service

The SM 111 cannot be serviced. Replace the SM 111 
in case of fault.

T

M

03

 40

85

 16

06

Pin

Type

Description

1

4-20 mA

Vibration sensor

2

4-20 mA

Additional input

3

13.5 VDC

Supply for 4-20 mA sensors, 
generated in SM 111

4

4-20 mA

Water-in-oil sensor

5

GND

Common ground for sensors

6

P5

Communication signal for IO 111

7

PE

Pump earth

8

P4

Supply for sensor board from 
IO 111

9

PTC

Thermistor PTC

10

Pt1000

Stator temperature

11

Digital input

12

Pt100

Main bearing temperature

13

Pt100

Support bearing temperature

14

Pt100

Stator temperature

1 2 3 4 5 6 7 8 9 1011 121314

TM

03

 4

086

 16

06

PE

T1 T2

G1 A1 G2 A2 K1 K2 R1 R2

D1 D2 D3 D4 D5 D6 D7 D8

P1 P2 P3 P4 P5

A Y B

I1 I2 I3

ON

DIP

1 2 3 4 5 6 7 8 9 10

DIP switch no. 9 on IO 111

Summary of Contents for SM 111

Page 1: ...GRUNDFOS INSTRUCTIONS SM 111 Installation and operating instructions...

Page 2: ......

Page 3: ...n y funcionamiento 25 Fran ais FR Notice d installation et de fonctionnement 28 Hrvatski HR Monta ne i pogonske upute 31 Italiano IT Istruzioni di installazione e funzionamento 34 Magyar HU Szerel si...

Page 4: ...sko SI Navodila za monta o in obratovanje 58 Srpski RS Uputstvo za instalaciju i rad 61 Suomi FI Asennus ja k ytt ohjeet 64 Svenska SE Monterings och driftsinstruktion 67 T rk e TR Montaj ve kullan m...

Page 5: ...ons des Etats membres CE relatives aux normes nonc es ci dessous Directive Basse Tension 2006 95 CE Norme utilis e EN 61010 1 2001 Directive Compatibilit Electromagn tique CEM 2004 108 CE Normes utili...

Page 6: ...1 na koji se ova izjava odnosi u skladu sa direktivama Saveta za uskla ivanje zakona dr ava lanica EU Direktiva niskog napona 2006 95 EC Kori en standard EN 61010 1 2001 EMC direktiva 2004 108 EC Kori...

Page 7: ...igh frequencies Use cable clamps as shown in fig 2 It is important to ensure a good electric contact from the mounting plate through the mounting screws to the metal cabinet of the frequency converter...

Page 8: ...s are connected correctly First time voltage is applied the SM 111 will read all inputs to detect which sensors are connected If a valid signal is measured the SM 111 will register that a sensor is pr...

Page 9: ...This product or parts of it must be disposed of in an environmentally sound way 1 Use the public or private waste collection service 2 If this is not possible contact the nearest Grundfos company or s...

Page 10: ...Appendix 74 Appendix 1 SM 111 mounted in a control panel TM03 8338 1007 M U V W L1 L2 L3 220Vac External safety wiring Internal safety wiring M U V W L1 L2 L3 220Vac 1 2 1 2 3 Optional ON 1 2 B...

Page 11: ...Appendix 75 SM 111 mounted in the pump TM03 8339 1007 M U V W L1 L2 L3 220Vac External safety wiring 1 2 1 2 3 5 4 Optional Internal safety wiring M U V W L1 L2 L3 220Vac ON 1 2 B...

Page 12: ...Appendix 76 SM 111 mounted on a DIN rail TM03 8039 0307 TM03 8040 0307 TM03 8040 0307...

Page 13: ...hone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA...

Page 14: ...kes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S Denmark All r...

Reviews: