46
23.7 Inputs and outputs
23.7.1 Mains supply (L1, L2, L3)
CUE on and off.
23.7.2 Motor output (U, V,
W)
1)
Output voltage in % of supply voltage.
2)
Depending on the pump family selected.
23.7.3 RS-485 GENIbus connection
The RS-485 circuit is functionally separated from other central
circuits and galvanically separated from the supply voltage
(PELV).
23.7.4 Digital inputs
All digital inputs are galvanically separated from the supply
voltage (PELV) and other high-voltage terminals.
23.7.5 Signal relays
1)
IEC 60947, parts 4 and 5.
The relay contacts are galvanically separated from other circuits
by reinforced insulation (PELV).
23.7.6 Analog inputs
1)
The factory setting is voltage signal "U".
All analog inputs are galvanically separated from the supply
voltage (PELV) and other high-voltage terminals.
23.7.7 Analog output
The analog output is galvanically separated from the supply
voltage (PELV) and other high-voltage terminals.
23.7.8 MCB 114 sensor input module
23.8 Sound pressure level
The sound pressure of the CUE is maximum 70 dB(A).
The sound pressure level of a motor controlled by a variable
frequency drive may be higher than that of a corresponding motor
which is not controlled by a variable frequency drive. See section
6.7 RFI filters
.
24.
Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
33
Supply voltage
200-240 V ± 10 %
Supply voltage
380-500 V ± 10 %
Supply voltage
525-600 V ± 10 %
Supply voltage
525-690 V ± 10 %
Supply frequency
50/60 Hz
Maximum temporary imbalance between
phases
3 % of rated value
Leakage current to ground
> 3.5 mA
Number of cut-ins, enclosure A
Max. 2 times/min.
Number of cut-ins, enclosures B and C
Max. 1 time/min.
Note
Do not use the power supply for switching the
Output voltage
0-100 %
1)
Output frequency
0-100 Hz
2)
Switching on output
Not recommended
Terminal number
68 (A), 69 (B), 61 GND (Y)
Terminal number
18, 19, 32, 33
Voltage level
0-24 VDC
Voltage level, open contact
> 19 VDC
Voltage level, closed contact
< 14 VDC
Maximum voltage on input
28 VDC
Input resistance, R
i
Approx. 4 k
Ω
Relay 01
, terminal number
1 (C), 2 (NO), 3 (NC)
Relay 02
, terminal number
4 (C), 5 (NO), 6 (NC)
Maximum terminal load (AC-1)
1)
240 VAC, 2 A
Maximum terminal load (AC-15)
1)
240 VAC, 0.2 A
Maximum terminal load (DC-1)
1)
50 VDC, 1 A
Minimum terminal load
24 V DC 10 mA
24 V AC 20 mA
C
= Common
NO = Normally open
NC = Normally closed
Analog input 1
, terminal number
53
Voltage signal
A53 = "U"
1)
Voltage range
0-10 V
Input resistance, R
i
Approx. 10 k
Ω
Maximum voltage
± 20 V
Current signal
A53 = "I"
1)
Current range
0-20, 4-20 mA
Input resistance, R
i
Approx. 200
Ω
Maximum current
30 mA
Maximum fault, terminals 53, 54
0.5 % of full scale
Analog input 2
, terminal number
54
Current signal
A54 = "I"
1)
Current range
0-20, 4-20 mA
Input resistance, R
i
Approx. 200
Ω
Maximum current
30 mA
Maximum fault, terminals 53, 54
0.5 % of full scale
Analog output 1
, terminal number
42
Current range
0-20 mA
Maximum load to ground
500
Ω
Maximum fault
0.8 % of full scale
Analog input 3
, terminal number
2
Current range
0/4-20 mA
Input resistance
< 200
Ω
Analog inputs 4 and 5
, terminal number
4, 5 and 7, 8
Signal type, 2- or 3-wire
Pt100/Pt1000
Note
When using Pt100 with 3-wire cable, the
resistance must not exceed 30
Ω
.
Subject to alterations.
Grundfos.bk Page 46 Friday, July 30, 2010 10:10 PM
Grundf
os CU
E
63