16
Fig. 34
Terminals for relay connection, B3
Fig. 35
Terminals for relay connection, B4
Fig. 36
Terminals for relay connection, C3 and C4, in the
upper right corner of the CUE
13.5 Connecting the MCB 114 sensor input module
The MCB 114 is an option offering additional analog inputs for the
CUE.
13.5.1 Configuration of the MCB 114
The MCB 114 is equipped with three analog inputs for these
sensors:
•
One additional sensor 0/4-20 mA.
See section
10.7.13 Sensor 2 (3.16)
.
•
Two Pt100/Pt1000 temperature sensors for measurement of
motor bearing temperature or an alternative temperature, such
as liquid temperature. See sections
10.7.18 Temperature
sensor 1 (3.21)
and
10.7.19 Temperature sensor 2 (3.22)
.
When the MCB 114 has been installed, the CUE will automatically
detect if the sensor is Pt100 or Pt1000 when it is switched on.
13.5.2 Wiring diagram, MCB 114
Fig. 37
Wiring diagram, MCB 114
Terminals 10, 11 and 12 are not used.
T
M
03 94
42 40
07
T
M
03
9441
4
00
7
T
M
03
9440
4
007
T
M
04 3
273 3
908
Terminal Type
Function
1 (VDO)
+24 V out Supply to sensor
2 (I IN)
AI 3
Sensor 2, 0/4-20 mA
3 (GND)
GND
Ground for analog input
4 (TEMP)
5 (WIRE)
AI 4
Temperature sensor 1, Pt100/Pt1000
6 (GND)
GND
Ground for temperature sensor 1
7 (TEMP)
8 (WIRE)
AI 5
Temperature sensor 2, Pt100/Pt1000
9 (GND)
GND
Ground for temperature sensor 2
1
9
8
7
6
5
4
3
2
1
2
1
1
1
0
VDO
I IN
GND
TEMP
WIRE
GND
TEMP
WIRE
GND
+
-
+