3.2 Location
IO 113 is only for indoor installation.
Pumps with sensors may, however, be installed in an
explosive environment provided that they have the
necessary product certification.
Safety information
IO 113 enclosure class is IP20.
It is designed to meet IEC-61010-2-030 concerning
measurement category II.
In order to meet the requirements of Pollution
Degree 2, install IO 113 in a protected environment
with enclosure class IPX4 or better according to IEC
60529. The cabinet must be of a flame-retardant
material.
Ambient temperature
-25 to +65 °C.
IO 113 must not be exposed to direct sunlight.
Installation altitude
Maximum 2000 m above sea level.
Relative humidity
Maximum 95 %.
3.3 Dimensions and mounting
Fig. 1
Module and DIN rail
IO 113 is prepared for mounting on a 35 mm DIN rail
(EN 50022).
Fit the IO 113 module by hooking the top onto the
DIN rail and clicking the bottom onto the rail.
Fig. 2
Mounting on DIN rail
The IO 113 module can be removed by pushing it
upwards and free of the DIN rail.
CAUTION
Explosive environment
Minor or moderate personal injury
- Do not install IO 113 in potentially
explosive environments.
ATEX/IEC Ex protection can be activated
by means of DIP switch 10. This enables
additional alarms, see section
DANGER
Electric shock
Death or serious personal injury
- Always install the product in a suitable
cabinet.
T
M
0
5
1
99
4
4
11
1
-
T
M
0
3
09
34
0
8
0
5
TM0
5
196
7 4
11
1
90
11
6
66.5
PE
T1 T2
G1 A1 G2 A2 K1 K2 R1 R2
D1 D2 D3 D4 D5 D6 D7 D8
P1 P2 P3 P4 P5
A Y B
I1 I2 I3
ON
DIP
1 2 3 4 5 6 7 8 9 10 11 12
Min. 30 mm
Min. 30 mm
35 mm DIN rail (EN 50022)
Recommended height: 7.5 mm
7.5