4
5
DPC is Digital Pump Controller, which is easy to use, programmable device for
single phase pumps (monoblock or submersible). It can be used to control the
pumps up to 15 Ampere.
APPLICATIONS:
DPC is very useful in water and wastewater applications, be it water transfer,
tank filling, tank emptying or even pressure boosting in Hydro-pneumatic
applications. It is an ideal choice in residential, industrial or institutional
segments where water and energy conservation is of utmost importance.
PARAMETER AND SPECIFICATIONS:
Following chart shows main technical parameters & specifications:
FEATURES:
LCD screen displays pump running information
Push button calibration
Overload protection
Motor stalled protection
Dry run protection without installing a f l oat
switch Under voltage protection (fixed settings)
Over voltage protection (fixed settings)
Transient surge protection
Memory function when power off & power recovery
Visual & audio alarm for fault prompt
DIP switch settings to make it suitable for different applications like water supply,
drainage or pressure boosting
Auto/Manual switch
Liquid level probes (in case of fully automatic models) for clear water
INTRODUCTION
Main technical characteristics
Control characteristic
Level control (with probes for clear
water or with floats)
Pressure control (with pressure switch)
Working modes
Manual/Auto
Main technical data
Rated output current (amperes)
1.5 to 15 A
Rated input voltage
AC 220V / 50 HZ / Single Phase
Trip response time of overload
5sec - 5min
Trip response time short circuit
Less than 0.1 sec
Trip response time of under/over voltage
Less than 5 sec
Trip response time of dry run
6 sec
Recovery time of overload
30 min
Recovery time of under/over voltage
5 min
Recovery time of dry run
30 min (or this can be set manually)
Trip voltage of over voltage
253 Volts
Trip voltage of under voltage
175 Volts
PROTECTIONS COVERED
Dry run (without float/probe)
Overload (auto calibrated or can be set)
Transient surge
Under voltage (fixed)
Over voltage (fixed)
Pump stalled
Short circuit
Other technical data
Permissible ambient temperature
Up to 55 Deg C
Degree of protection
IP 54
Install position
Vertical
Unit dimensions (L X W X H)
225 x 225 x 100 mm
Unit weight
1.5kg