14

 

15

 

 

 

  DRAINAGE APPLICATION BY INSTALLING FLOAT SWITCH 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

 

(g)

 

Application: Pressure boosting (using pressure switch) 

Start condition: 

Pressure in the pipe line is less than the set point of pressure 

switch, relay contact of pressure switch is ON and liquid level in the well/supply 

tank is above lower probe (Float switch up position), the controller will run the 

pump.

 

 

Stop condition: 

Pressure has reached the set point of pressure switch; relay 

contact of pressure switch is OFF; the controller will stop the pump.

 

 

Probe/sensor free application in case of submersible pumps: 

The unit has 

reliable and automatic protection against dry running if it is used for 

submersible pump for deep well. Users can short the terminals 1, 2 & 3 to 

achieve sensor free dry run protection.

 

(h)

 

Application: Irrigation/sewage/drainage (using float switch) 

 

Start condition: 

When the “Float switch A” reaches at up position, the 

controller will run the pump.

 

 

Stop condition: 

When the “Float switch A”  reaches at down position, the 

controller will stop the pump.

 

 

Over  f l ow alarm: 

In case the level in the sump rises even if the pump is 

draining water and the “Float switch B”  reaches at up position, the controller 

will sound the over  f l ow alarm to warn the pump operator.

 

 

Meaning of the messages & graphics displayed on the LCD screen

 

FULL

 

Pressure has reached set point and pump has 

stopped.

 

DRY RUN

 

Liquid level in the borewell is below the pump 

intake, pumps stop running.

 

 

NO WATER

 

Liquid level in the underground tank/water 

well is below lower most probe (float switch: 

down position), pump stops.

 

 

 

Wiring diagram

 

Pressure switch

 

#2 

#1

 

Adjustable spring

 

+  +

 

+  +

 

Internal capacitance 

“store”button

 

O N 

“liquid/pressure”

 

1  2 

SWITCH

 

N1  L1  C

 

M

 

Pump

 

Short circuit

 

L  PE

 

AC200V

 

Wiring diagram

 

Internal capacitance

 

O N 

P

“liquid/pressure”

 

“store”button

 

1  2 

L

 

SWITCH

 

N1  L1  C

 

   

 

N  L  PE

 

AC200V

 

M

 

Pump

 

Sewage tank

 

PRESSURE BOOSTING APPLICATION BY INSTALLING 

PRESSURE SWITCH

 

St

op

 co

nt

ac

t

 

Com
 co

nt

ac

t

 

Meaning of the messages & graphics displayed on the LCD screen

 

FULL

 

“Float switch A” 

reaches up position, pump 

starts running.

 

DRY RUN

 

Liquid level in the sump is below the pump 

intake, pumps stop running.

 

NO WATER

 

“Float switch A” 

reaches down position, pump 

stops.

 

OVER FLOW

 

“Float switch B” 

reaches up position, controller 

will sound and alarm.

 

 

Summary of Contents for DPC 1-1

Page 1: ...struction DPC 1 1 For Single Phase Pumps up to 15A For more information contact us The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide ...

Page 2: ...ling probes or float switch 12 Pressure boosting application by installing pressure switch 14 Drainage application by installing float switch 15 BASIC OPERATION 16 Manual mode 16 Auto mode 16 Faults protection 17 CAPACITOR 1 8 Capacitor ratings as per motor kW 18 Mounting instructions 18 TROUBLE SHOOTING 1 9 PRODUCT SELECTION 20 SAFETY CAUTION If these safety instructions are not observed it may r...

Page 3: ... applications like water supply drainage or pressure boosting Auto Manual switch Liquid level probes in case of fully automatic models for clear water INTRODUCTION Main technical characteristics Control characteristic Level control with probes for clear water or with floats Pressure control with pressure switch Working modes Manual Auto Main technical data Rated output current amperes 1 5 to 15 A ...

Page 4: ... the right tools according to your own experience LCD SCREEN Minute Second Hour Voltage Ampere CONTROLLER COMPONENTS DIP SWITCH SETTINGS Users can set the function switch to suit different applications Before setting the function switch the unit should be disconnected from the power supply After completing the settings of dip switches power may be applied to the unit Following signs will be displa...

Page 5: ...ual mode Make sure the pump is not running and LCD screen looks as shown on the left FLASH 2 243V 1 7A RUN No Caliber No Water Manual FLASH Press the START key to run the pump confirm the pump is running OK and drawing rated current Also confirm the mains supply is healthy and incoming voltage is normal LCD screen will display voltage and current being drawn by pump 3 08S RUN Again press START key...

Page 6: ... probe In the event of risk of electric storms lightning or when liquid medium in well or tank or sump is very dirty it is recommended oat switch is used not running Press the STOP key approximately for 3 secs and release when the unit makes a Beep sound c Liquid level probe installation FLOAT SWITCH INSTALLATION If the oat switch is equipped withthree wires use the BLACK Unit is now back to facto...

Page 7: ...inals 1 2 3 to achieve sensor free dry run protection Meaning of the messages graphics displayed on the LCD screen TANK FULL Liquid level in the overhead tank has reached upper probe float switch up position pump stops DRY RUN Liquid level in the borewell is below the pump intake pumps stops running NO WATER Liquid level in the underground tank water well is below lower most probe float switch dow...

Page 8: ...arm In case the level in the sump rises even if the pump is draining water and the Float switch B reaches at up position the controller will sound the over f l ow alarm to warn the pump operator Meaning of the messages graphics displayed on the LCD screen FULL Pressure has reached set point and pump has stopped DRY RUN Liquid level in the borewell is below the pump intake pumps stop running NO WAT...

Page 9: ...overs automatically until all the abnormal conditions have been cleared However the recovery time of the control unit is different for different faults Details of recovery times for each fault have already been explained in this manual Recovery time for dry run and overload can be altered and set as per needs However recovery times and values for under and over voltage are factory NOTE In the mode...

Page 10: ... Open the top cover gently using normal star screwdriver While opening the cover make sure you don t damage the existing clip type probes which is connected to the back of the cover House the capacitor inside the holder by lifting the left side of the clamp and press it after inserting the capacitor as shown in the Figure 1 and 2 Connect the capacitor cables to the specified terminal by gently bri...

Page 11: ...rrent is higher than the calibrated current pump is in over load protection state Control unit will attempt to restart the pump every 30 minutes until running current is restored to normal Pump impeller is jammed pump motor dragging pump bearing broken Check pump impeller or bearing Flashing of NO CALIBER Parameter calibration not completed Carry out parameter calibration Flashing of DRY RUN Liqui...

Reviews: