CUE
p
Constant pressure
The pressure is kept
constant,
independently of the
flow rate.
CUE
p
Constant pressure
with stop function
The outlet pressure
is kept constant at
high flow rate. On/off
operation at low flow
rate.
CUE
L
Constant level
The liquid level is
kept constant,
independently of the
flow rate.
CUE
L
Constant level with
stop function
The liquid level is
kept constant at high
flow rate.
On/off operation at
low flow rate.
Q
CUE
Constant flow rate
The flow rate is kept
constant,
independently of the
head.
CUE
t
Constant
temperature
The liquid
temperature is kept
constant,
independently of the
flow rate.
Related information
9. Setting the product
For correct programming, it is often necessary to make settings in
several submenus. The programmed data is saved internally in the
frequency converter.
It is possible to make a backup of the data by uploading them to the
operating panel's memory.
The menus are accessed or changed from the [Main Menu] or
[Favourites] on the operating panel. However, not all menus are
available in [Favourites].
All settings that have been made are visible in [Favourites]
Q5
>
Changes Made
.
Related information
9.1 First-time setup via the startup guide
The startup guide starts automatically the first time the product is
switched on or after startup of the frequency converter. The guide
enables quick configuration of basic pump- and application
parameters.
Make sure that the equipment connected is ready for
startup.
Make sure that CUE is connected to the power supply.
Make sure that you have the nameplate data
for the motor, pump and CUE, since you need to enter
some data during startup.
Reactivate the startup guide by pressing [Favourites]
Q4
>
Run start-up guide
1. Press
OK
to begin the startup guide. Follow the on-screen
instructions to complete the commissioning of the frequency
converter. Some data from the motor nameplate is needed.
Welcome to the CUE Start-
up guide. Press OK to
continue
Start-up Guide
TM077488
Welcome screen
2. Press
OK
to choose the desired language then the down arrow
key for the coming steps.
1(1)
Please select language:
English
Start-up Guide
TM077489
Language
3. Select the unit type depending on the region where CUE is
installed.
1(1)
Please select units used
for setup
Metric
Start-up Guide
TM077490
Units
4. Select a specific pump type, or select "Other" for an unrestricted
setting.
1(1)
Please select the pump you
are running or select other
for unrestrichted settings
Other
Start-up Guide
TM077491
Pump types
26