5. Select the required motor type (Asynchronous motor, PM
Assisted Sync. Reluctance motor, IPM motor, SPM motor) and
follow the startup guide. It is possible to skip the motor settings
and the thermal protection parameters. Based on the motor
type, the related parameters appear for adjustment.
1(1)
Please select the motor of
the pump or select “skip
motor setup”
Asynchronous motor
Start-up Guide
TM077492
Motor types
6. If there is a sine-wave filter installed, select "Yes" and define
the switching frequency on the next screen. In the example
below, it is assumed that there is no sine-wave filter installed.
1(1)
Do you have a Sine-wave
filter connected on the
output?
No
Start-up Guide
TM077493
Sine-Wave filter
7. The motor should be properly connected to CUE. AMA
measures the electrical characteristics of the motor to provide
an accurate electronic model of the motor and does not cause
the motor to run. By selecting "Yes", you can go to the next
steps.
1(1)
Run an automatic motor
adaptation (AMA)
procedure?
No
Start-up Guide
TM077494
Run AMA
8. Enter the acceleration time from 0 RPM to the rated motor
speed and the deceleration time from the rated motor speed to 0
RPM.
1(1)
Acceleration time
Deceleration time
1.00s
3.00s
Start-up Guide
TM077510
Acceleration and deceleration time
9. Enter the ramp time between 0 RPM and the minimum speed.
1(1)
Enter the acceleration time
used below min. Speed
1.00s
Start-up Guide
TM07751
1
Initial ramp time
10. The direction of rotation is set for CUE by default. If needed,
double-check the direction of rotation by selecting "Yes", and
follow the coming steps. If "Other" pump type is selected,
there are two screens after the direction check:
Min. frequency and Max. frequency.
1(1)
Do you want to check the
motors rotation?
No
Start-up Guide
TM077512
Direction of rotation check
11. Select the relevant control mode for the desired application. It
is preset according to the pump type selected by the user.
1(1)
Enter control mode for closed
loop applications or open loop
for constant curve or standby
pumps
Const. pressure
Start-up Guide
TM077549
Control mode
12. This screen is shown if the user has chosen one of the closed-
loop control modes.
1(1)
Feedback Sensor Range
(Terminal 54)
0-6 bar
Start-up Guide
TM077550
Feedback sensor range
13. After choosing the sensor range, the user needs to select the
electrical signal range that should be selected according
to the dip-switch adjustment.
1(1)
Feedback Sensor Type
(Terminal 54)
4-20mA
Start-up Guide
TM077551
Feedback sensor type
14. The setpoint can be influenced by the external setpoint
input, and the electrical signal must be configured in this step.
1(1)
Configure External
Setpoint?
0-10 V
Start-up Guide
TM077552
External setpoint configuration
27
English (GB)