39 42 50 53 54 55
61 68 69
61 68 69
12 13 18 19 27 29 32 33 20 37
A53
U I U I
A54
TM075269
3-wire sensor
Terminal
Type
Function
12
+24 V out
Supply to sensor
13
+24 V out
Additional supply
18
DI 1
Digital input, programmable
19
DI 2
Digital input, programmable
20
GND
Common frame for digital inputs
27
DI/O 1
Digital input/output,
programmable
29
DI/O 2
Digital input/output,
programmable
32
DI 3
Digital input, programmable
33
DI 4
Digital input, programmable
37
Safe stop
Safe stop
39
GND
Frame for analog output
42
AO 1
Analog output, 0-20 mA
50
+10 V out
Supply to potentiometer
53
AI 1
External setpoint, 0-10 V, 0/4-20
mA
54
AI 2
Sensor input, sensor 1, 0/4-20
mA
55
GND
Common frame for analog
inputs
61
RS-485 GND Y GENIbus, frame
68
RS-485 A
GENIbus, signal A (+)
69
RS-485 B
GENIbus, signal B (-)
The RS-485 screen must be connected to the frame.
6.7.2 Connection of a thermistor (PTC) to CUE
A PELV circuit provides protection against electric shock. Special
connection requirements apply to this type of circuit. The
requirements are described in EN 61800-5-1.
In order to maintain PELV, all connections made to the control
terminals must be PELV. For example, the thermistor must have
reinforced or double insulation.
6.7.2.1 Accessing the signal terminals
All signal terminals are behind the terminal cover on the front side
of CUE. Remove the terminal cover as shown in the figures below.
TM039003
Access to signal terminals, A2 and A3
TM039004
Access to signal terminals, A4, A5, B1, B2, B3, B4, C1, C2, C3
and C4