11.7 BM hp circulation pump

This section and the subsequent subsections make references to 
the piping and instrumentation diagram, fig. 12.

To start up the BM hp circulation pump, proceed as follows:

1. Open the solenoid valve (V4) on the BM hp circulation pump 

(P4). 

2. Ensure an inlet pressure on the pump (min. 1 bar and 

max. 80 bar).

3. Wait 3 to 5 minutes to ensure optimum venting.

4. Close the solenoid valve on the BM hp circulation pump. 

5. Start the BM hp circulation pump.

In systems involving the risk of water hammer in connection with 
start/stop, the necessary measures must be taken to reduce this 
risk, e.g. by installing a diaphragm tank.

During operation, the inlet pressure must be checked in 
accordance with section 

11.5 Operation settings

The BM hp circulation pump is now ready for operation.

11.7.1 Checking the direction of rotation

Procedure: 

1. Close the control valve (V2) on the discharge side of the 

BM hp circulation pump (P4) to approx. 1/3 of maximum flow. 

2. Start the BM hp circulation pump, and record discharge 

pressure and flow readings. 

3. Stop the pump, and interchange two of the phases to the 

motor. 

4. Restart the pump, and re-record discharge pressure and flow 

readings. 

5. Stop the pump. 

6. Compare the results recorded under points 2 and 4. The 

connection which gave the larger pressure and flow is the 
correct direction of rotation. 

The check of the direction of rotation should last for the shortest 
possible time.

12. Checking the operation of the BMPX system

Check the following at suitable intervals:

Flow and pressure.

Current consumption.

Pressure drop over the prefilter.
Replace the filter element when "clogged filter" is indicated.

Whether the motor ball bearings are worn.

Whether the shaft seal is leaky. 
The shaft seal is lubricated by the pumped liquid. Small 
quantities of liquid are therefore drained via the drain hole in 
the coupling housing.

Whether the sound pressure level has changed.

It is recommended to write the operating data in the log books 
supplied with the system. The data can be useful for maintenance 
purpose. The log books are shown on pages 91 to 93.

13. Maintenance

See installation and operating instructions for BMP pumps.

14. Motor bearings

Under optimum operating conditions, the operating life of the 
motor ball bearings is approx. 20,000 operating hours. After that 
period, the bearings must be replaced. The new bearings must be 
filled with grease.

15. Shut-down procedure

See section 

16. Periods of inactivity

 for precautions to be taken 

when shutting down the system.

1. If operated by variable-frequency drive, speed down the BMP 

hp feed pump (P3) until the system pressure drops below 
28 bar. 
If not operated by variable-frequency drive, open the solenoid 
valve (V4) until the pressure is below 28 bar and go to step 2.

2. Stop the BMP hp feed pump (P3), followed by the BM hp 

circulation pump (P4), and stop the sea-water feed pump (P1).

Caution:

 To prevent overflow, make sure that the flow through 

the X-Changer is reduced by throttling the low-pressure reject-
water valve (V3).

16. Periods of inactivity

In the case of periods of inactivity, various precautions must be 
taken to protect the system and ensure long life.

The precautions to be taken if the system is to be inactive for a 
certain period appear in the table: 

* Use the same solution that is used to preserve the membranes.

For further information on anti-freeze liquids, please contact 
Grundfos.

16.1 Start-up after a period of inactivity

The precautions to be taken if the system has been inactive for 
a certain period appear in the table: 

Note

The BM hp circulation pump must be filled with 
water before start-up.

Warning

The BM hp circulation pump is not allowed to run 
against a closed discharge valve for more than 
5 seconds as this will cause an increase in 
temperature/formation of steam in the pump 
which may cause damage to the pump and motor.

If there is any risk of the BM hp circulation pump 
running against a closed discharge valve or no 
flow, a minimum liquid flow through the pump 
should be ensured by connecting a bypass/a 
drain to the discharge side of the pump. The 
drain can for instance be connected to a tank.

The solenoid valve must be opened three times 
a day (every 8 hours) for 30 seconds at a time.

Action

30 min.

1 month

3 months

6 months

Flushing

x

x

x

x

Fill the pumps with fresh water

x

x

x

x

Preserve the pump*

x

x

x

Note

The normal stop procedure must be followed 
step by step.

Caution

Never just drain the pump! 

Action

30 mi

n.

1 month

3 months

6 months

Vent air from the system

x

x

x

x

Check the flows FM2 and FM3

x

x

x

Note

The normal start-up procedure must be followed 
step by step.

Summary of Contents for BMPX

Page 1: ...BMPX GRUNDFOS INSTRUCTIONS Installation and operating instructions ...

Page 2: ...nsiglio concernente il ravvicinamento delle legislazioni degli Stati membri CE relative a Macchine 98 37 CE Materiale elettrico destinato ad essere utilizzato entro certi limiti di tensione 2006 95 CE Standard usati EN 60335 1 2002 e EN 60335 2 41 2003 Compatibilità elettromagnetica 2004 108 CE Standard usati EN 61000 6 2 e EN 61000 6 3 Declaración de Conformidad Nosotros Grundfos declaramos bajo ...

Page 3: ...s 4 Montage und Betriebsanleitung 16 Notice d installation et d entretien 29 Istruzioni di installazione e funzionamento 41 Instrucciones de instalación y funcionamiento 53 Οδηγίες εγκατάστασης και λειτουργίας 65 Monterings og driftsinstruktion 79 ...

Page 4: ...e BMPX units are supplied from factory in boxes in which they must remain until they are to be installed The units are ready for installation 3 Commissioning Commissioning of the BMPX booster system must be carried out by competent and certified Grundfos employees to ensure long and trouble free operation The commissioning includes training on site of the people maintaining and monitoring the syst...

Page 5: ...Changer Check that all nuts are tightened 7 Installation The BMP hp feed pump and X Changer are delivered separately without any kind of base frame The installation must be carried out according to local regulations and in such a way that proper and reliable operation can be obtained 7 1 BMP hp feed pump The inlet port is marked with an I and the discharge port with an O Fig 2 BMP hp feed pump and...

Page 6: ...ms for the motor protection starter and monitoring devices used See fig 7 The electrical connections must be made in the terminal box Fig 7 Wiring diagram BMP hp feed pump The required voltage quality measured at the motor terminals is 10 6 of the rated voltage during continuous operation including variation in the supply voltage and losses in cables It must be checked that there is voltage symmet...

Page 7: ...ice 9 1 4 Thermistor If thermistors are used as protection they must be connected to terminals T1 and T2 before start up See fig 7 9 2 BM hp circulation pump The electrical connection must be carried out by an authorised electrician in accordance with local regulations The required voltage quality measured at the motor terminals is 10 6 of the rated voltage during continuous operation including va...

Page 8: ...unit should be set as above but the maximum setting should be as follows Starter overload setting rated current I1 1 ISFA x 0 58 The maximum permissible run up changeover time for star delta starting is 2 seconds 10 Before starting the BMPX Check the following Electricity supply in accordance with nameplate Pipework according to the diagram fig 12 Functionality of the solenoid valve BM hp circulat...

Page 9: ...ge flow equals the high pressure brine inlet flow 11 4 Low pressure flow control The low pressure reject water valve V3 on the discharge side of the system must be adjusted to control the flow rate of the low pressure sea water inlet and low pressure brine discharge This valve also adds back pressure on the X Changer required to prevent destructive cavitation The low pressure sea water inlet flow ...

Page 10: ...rating conditions the operating life of the motor ball bearings is approx 20 000 operating hours After that period the bearings must be replaced The new bearings must be filled with grease 15 Shut down procedure See section 16 Periods of inactivity for precautions to be taken when shutting down the system 1 If operated by variable frequency drive speed down the BMP hp feed pump P3 until the system...

Page 11: ...must be observed to ensure sufficient cooling of the motor Recommended flow rates at 25 C 77 F Type of BM hp m3 h US GPM 50 Hz 60 Hz 50 Hz 60 Hz BM 5A 3 2 5 6 3 3 6 4 14 25 14 28 BM 8A 5 9 5 7 9 22 48 30 40 BM 17 8 24 8 29 35 106 35 128 BM 30 15 38 18 45 66 167 79 198 Maximum permissible liquid temperature Motor Maximum liquid temperature Minimum flow velocity past the motor Minimum flow C F m s f...

Page 12: ...ons 9 2 2 Motor protection and 11 Start up and operation c The magnetic coil in the motor starter contactor is defective not cutting in Replace the coil Check the coil voltage d The control circuit has cut out or is defective Check the control circuit and the contacts in the monitoring devices low pressure switch level switch etc e The motor supply cable is defective Check motor and cable See sect...

Page 13: ...unit has tripped out Reset the starter overload If it trips out again the voltage should be checked c The magnetic coil of the motor starter contactor is short circuited not cutting in Replace the coil Check the coil voltage d The control circuit has cut out or is defective Check the control circuit and the contacts in the monitoring devices pressure switch flow switch etc e The motor supply cable...

Page 14: ...an high pressure flow resulting in mixing and high feed water salinity See section 11 6 Balancing the X Changer 3 High salinity in high pressure sea water feed stream a Unbalanced system See section 11 6 Balancing the X Changer b A jammed or stalled rotor short circuits high pressure reject water with high pressure feed water No exchange occurs no audible rotation See fault number 5 4 Low pressure...

Page 15: ...the phase with the highest amp consumption and the one with the lowest amp consumption must not exceed 10 of the lowest amp consumption If so or if the current exceeds the rated current check these possible faults A damaged pump is causing the motor to be overloaded Pull the pump out of the sleeve for overhaul The motor windings are short circuited or partly disjointed Too high or too low supply v...

Page 16: ... to support any warranty claims Initial data must be submitted within 24 hours of start up Product no Installation date Company your ref Country Type Start of operation City VFD Soft start Brand Date Amb temp Liquid temp Inlet pressure Discharge pressure Flow Current A Voltage V Comments ...

Page 17: ...o support any warranty claims Initial data must be submitted within 24 hours of start up Product no Installation date Company your ref Country Type Start of operation City VFD Soft start Brand Date Amb temp Liquid temp Feed flow pressure Discharge flow pressure Current A Voltage V Comments ...

Page 18: ...a must be submitted within 24 hours of start up Model of X Changer Company your ref Country Start of operation City Serial number Units please circle bar m3 h psi gpm Date Total hours HP inlet pressure HP discharge pressure LP inlet pressure LP discharge pressure HP flow LP flow LP inlet salinity HP discharge salinity ...

Page 19: ...94 ...

Page 20: ...Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60 LV 1035 Rīga Tālr 371 714 9640 7 149 641 Fakss 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g 6 LT 03201 Vilnius Tel 370 52 395 430 Fax 370 52 395 431 Malaysia GRUNDFO...

Page 21: ...www grundfos com Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence 96770338 1007 156 ...

Reviews: