Grundfos BMPX Installation And Operating Instructions Manual Download Page 9

9

11. Start-up and operation

11.1 BMPX

This section and the subsequent subsections make references to 
the piping and instrumentation diagram, fig. 12.

1.

All valves should be in their normal operating positions.

2.

Start the sea-water feed pump (P1) with flow through the 
X-Changer (X1) and through the bypass of the BMP hp feed 
pump (P3).

3.

Start the BM hp circulation pump (P4) as soon as pressure 
has built up in the system. See section 

11.7 BM hp circulation 

pump

.

4.

Vent air from the system. Open the solenoid valve (V4) on the 
BM hp circulation pump (P4) and slacken the vent plugs on 
the BMP hp feed pump (P3). Let the pump run with sea water 
for 5 minutes to ensure that all air is released. Close the 
solenoid valve on the BM hp circulation pump and retighten 
the vent plugs on the BMP hp feed pump.

5.

Adjust the low-pressure reject-water valve (V3) on the 
discharge side of the X-Changer (X1) until the low-pressure 
sea-water inlet flow (FM2) equals the calculated sea-water 
discharge flow (FM3).

6.

Adjust the variable-frequency drive on the BM hp circulation 
pump (P4) or control valve (V2) until the desired flow rate is 
achieved as indicated by the high-pressure flowmeter (FM3). 
FM3 = FM2 (= balanced flow). See sectio

11.6 Balancing the 

X-Changer

 for important and detailed information.

7.

All flows in and out of the X-Changer (X1) should be balanced 
to within 5 % for optimum operation.

Note:

 If any doubt exists in reading the flowmeter, the low-

pressure sea-water inlet should be the greater of the two 
flows (FM2 > FM3). Zero mixing can be achieved by flowing 
the sea-water inlet approximately 10 % higher than the sea-
water discharge.

8.

Start the BMP hp feed pump (P3).

9.

Finally, the BMPX system will produce the permeate flow 
equal to the flow from the BMP hp feed pump.
The sound pressure level from the X-Changer (X1) will 
increase. Small variations in sound pressure level and rotor 
speed are normal.

Caution:

 The low-pressure and high-pressure flows through 

the X-Changer must never exceed the rated maximum flow 
for the chosen X-Changer.

10. The variable-frequency drive feedback for the BM hp 

circulation pump (P4) can be switched to automatic control 
using FM2 compared to FM3. The solenoid valve (V4) must 
be opened three times a day (every 8 hours) for 30 seconds 
to allow flushing of stagnant sea water in the BM hp 
circulation pump (P4).

11.2 Flow control and balancing

Flow rates and pressures in a typical BMPX system vary slightly 
over the life of the system due to temperature variations, 
membrane fouling or feed salinity variations. The X-Changer rotor 
is powered by the flow of liquid through the unit. The speed of the 
rotor is self-adjusting over the operating range of the X-Changer.

11.3 High-pressure flow control

The flow through the BM hp circulation pump (P4) is adjusted with 
the control valve (V2) or a variable-frequency drive to control the 
flow rate of the high-pressure sea-water discharge from the 
X-Changer and high-pressure brine inlet to the X-Changer. The 
high-pressure sea-water discharge flow equals the high-pressure 
brine inlet flow.

11.4 Low-pressure flow control

The low-pressure reject-water valve (V3) on the discharge side of 
the system must be adjusted to control the flow rate of the low-
pressure sea-water inlet and low-pressure brine discharge. This 
valve also adds back-pressure on the X-Changer required to 
prevent destructive cavitation. The low-pressure sea-water inlet 
flow equals the high-pressure brine-reject water inlet flow.

11.5 Operation settings

The flow and discharge pressure of the BMPX system should 
always be kept within the ranges for which it was originally 
designed. See the "Technical specification" supplied with the 
system.

If the system requires flows and pressures outside the design 
range, changes are possible. Please contact Grundfos.

11.6 Balancing the X-Changer 

This section and the subsequent subsections make references to 
the piping and instrumentation diagram, fig. 12.

1. Start the sea-water feed pump (P1).

2. Adjust the low-pressure reject-water valve (V3) on the 

discharge side of the X-Changer (X1) until the low-pressure 
sea-water inlet flow (FM2) equals the calculated sea-water 
discharge flow (FM3).

3. Start the BM hp circulation pump (P4). See section 

11.7 BM 

hp circulation pump

.

4. Adjust the variable-frequency drive on the BM hp circulation 

pump (P4) or control valve (V2) until the desired flow rate is 
achieved as indicated by the high-pressure flowmeter (FM3). 
FM3 = FM2 (= balanced flow).

To achieve balanced flow through the X-Changer (X1), use 
flowmeters installed on the low-pressure sea-water inlet piping 
and high-pressure sea-water discharge piping. All flows in and 
out of the X-Changer should be balanced to within 5 % for 
optimum operation.

The X-Changer is designed to operate at liquid mixing levels 
below 5 %. Balanced flows control the mixing of concentrate with 
the feed. Zero mixing can be achieved by flowing the sea-water 
inlet approximately 10 % higher than the sea-water discharge. 
Flowing the sea-water inlet much less than the sea-water 
discharge will result in lower-quality permeate, increased feed 
pressure and higher energy consumption.

Recommended practice for the BM hp circulation pump is to use 
a slightly oversized pump to handle projected membrane 
concentrate flows, taking into account seasonal variations, 
membrane fouling and manifold losses. The flow and pressure of 
the BM hp circulation pump can be controlled with a variable-
frequency drive (P4) or control valve (V2).

Caution

It may be necessary to let the BMP hp feed pump 
(P3) run at minimum speed (to vent the system). 
If so, the solenoid valve (V4) on the BM hp 
circulation pump must be open.

Note

The following procedure should be applied to 
achieve balanced flows. 

Note

If any doubt exists in reading the flowmeter, the 
low-pressure sea-water inlet should be the 
greater of the two flows (FM2 > FM3).

Caution

Operating the X-Changer with unbalanced flows 
may result in contamination of the sea-water feed 
by the brine reject.

Caution

The low-pressure and high-pressure flows 
through the X-Changer must never exceed the 
rated maximum flow. The only reliable way to 
determine this flow is to use a low-pressure 
flowmeter (FM2) or a high-pressure flowmeter 
(FM3), respectively.

Summary of Contents for BMPX

Page 1: ...BMPX GRUNDFOS INSTRUCTIONS Installation and operating instructions ...

Page 2: ...nsiglio concernente il ravvicinamento delle legislazioni degli Stati membri CE relative a Macchine 98 37 CE Materiale elettrico destinato ad essere utilizzato entro certi limiti di tensione 2006 95 CE Standard usati EN 60335 1 2002 e EN 60335 2 41 2003 Compatibilità elettromagnetica 2004 108 CE Standard usati EN 61000 6 2 e EN 61000 6 3 Declaración de Conformidad Nosotros Grundfos declaramos bajo ...

Page 3: ...s 4 Montage und Betriebsanleitung 16 Notice d installation et d entretien 29 Istruzioni di installazione e funzionamento 41 Instrucciones de instalación y funcionamiento 53 Οδηγίες εγκατάστασης και λειτουργίας 65 Monterings og driftsinstruktion 79 ...

Page 4: ...e BMPX units are supplied from factory in boxes in which they must remain until they are to be installed The units are ready for installation 3 Commissioning Commissioning of the BMPX booster system must be carried out by competent and certified Grundfos employees to ensure long and trouble free operation The commissioning includes training on site of the people maintaining and monitoring the syst...

Page 5: ...Changer Check that all nuts are tightened 7 Installation The BMP hp feed pump and X Changer are delivered separately without any kind of base frame The installation must be carried out according to local regulations and in such a way that proper and reliable operation can be obtained 7 1 BMP hp feed pump The inlet port is marked with an I and the discharge port with an O Fig 2 BMP hp feed pump and...

Page 6: ...ms for the motor protection starter and monitoring devices used See fig 7 The electrical connections must be made in the terminal box Fig 7 Wiring diagram BMP hp feed pump The required voltage quality measured at the motor terminals is 10 6 of the rated voltage during continuous operation including variation in the supply voltage and losses in cables It must be checked that there is voltage symmet...

Page 7: ...ice 9 1 4 Thermistor If thermistors are used as protection they must be connected to terminals T1 and T2 before start up See fig 7 9 2 BM hp circulation pump The electrical connection must be carried out by an authorised electrician in accordance with local regulations The required voltage quality measured at the motor terminals is 10 6 of the rated voltage during continuous operation including va...

Page 8: ...unit should be set as above but the maximum setting should be as follows Starter overload setting rated current I1 1 ISFA x 0 58 The maximum permissible run up changeover time for star delta starting is 2 seconds 10 Before starting the BMPX Check the following Electricity supply in accordance with nameplate Pipework according to the diagram fig 12 Functionality of the solenoid valve BM hp circulat...

Page 9: ...ge flow equals the high pressure brine inlet flow 11 4 Low pressure flow control The low pressure reject water valve V3 on the discharge side of the system must be adjusted to control the flow rate of the low pressure sea water inlet and low pressure brine discharge This valve also adds back pressure on the X Changer required to prevent destructive cavitation The low pressure sea water inlet flow ...

Page 10: ...rating conditions the operating life of the motor ball bearings is approx 20 000 operating hours After that period the bearings must be replaced The new bearings must be filled with grease 15 Shut down procedure See section 16 Periods of inactivity for precautions to be taken when shutting down the system 1 If operated by variable frequency drive speed down the BMP hp feed pump P3 until the system...

Page 11: ...must be observed to ensure sufficient cooling of the motor Recommended flow rates at 25 C 77 F Type of BM hp m3 h US GPM 50 Hz 60 Hz 50 Hz 60 Hz BM 5A 3 2 5 6 3 3 6 4 14 25 14 28 BM 8A 5 9 5 7 9 22 48 30 40 BM 17 8 24 8 29 35 106 35 128 BM 30 15 38 18 45 66 167 79 198 Maximum permissible liquid temperature Motor Maximum liquid temperature Minimum flow velocity past the motor Minimum flow C F m s f...

Page 12: ...ons 9 2 2 Motor protection and 11 Start up and operation c The magnetic coil in the motor starter contactor is defective not cutting in Replace the coil Check the coil voltage d The control circuit has cut out or is defective Check the control circuit and the contacts in the monitoring devices low pressure switch level switch etc e The motor supply cable is defective Check motor and cable See sect...

Page 13: ...unit has tripped out Reset the starter overload If it trips out again the voltage should be checked c The magnetic coil of the motor starter contactor is short circuited not cutting in Replace the coil Check the coil voltage d The control circuit has cut out or is defective Check the control circuit and the contacts in the monitoring devices pressure switch flow switch etc e The motor supply cable...

Page 14: ...an high pressure flow resulting in mixing and high feed water salinity See section 11 6 Balancing the X Changer 3 High salinity in high pressure sea water feed stream a Unbalanced system See section 11 6 Balancing the X Changer b A jammed or stalled rotor short circuits high pressure reject water with high pressure feed water No exchange occurs no audible rotation See fault number 5 4 Low pressure...

Page 15: ...the phase with the highest amp consumption and the one with the lowest amp consumption must not exceed 10 of the lowest amp consumption If so or if the current exceeds the rated current check these possible faults A damaged pump is causing the motor to be overloaded Pull the pump out of the sleeve for overhaul The motor windings are short circuited or partly disjointed Too high or too low supply v...

Page 16: ... to support any warranty claims Initial data must be submitted within 24 hours of start up Product no Installation date Company your ref Country Type Start of operation City VFD Soft start Brand Date Amb temp Liquid temp Inlet pressure Discharge pressure Flow Current A Voltage V Comments ...

Page 17: ...o support any warranty claims Initial data must be submitted within 24 hours of start up Product no Installation date Company your ref Country Type Start of operation City VFD Soft start Brand Date Amb temp Liquid temp Feed flow pressure Discharge flow pressure Current A Voltage V Comments ...

Page 18: ...a must be submitted within 24 hours of start up Model of X Changer Company your ref Country Start of operation City Serial number Units please circle bar m3 h psi gpm Date Total hours HP inlet pressure HP discharge pressure LP inlet pressure LP discharge pressure HP flow LP flow LP inlet salinity HP discharge salinity ...

Page 19: ...94 ...

Page 20: ...Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60 LV 1035 Rīga Tālr 371 714 9640 7 149 641 Fakss 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g 6 LT 03201 Vilnius Tel 370 52 395 430 Fax 370 52 395 431 Malaysia GRUNDFO...

Page 21: ...www grundfos com Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence 96770338 1007 156 ...

Reviews: