Installation
24 | 80
B
A
_
T
D3
-B
M
0
0
2
e
n
_
0
0
4
_
so
ft
liQ
-MD
4.3.3
Establish waste water connection as per DIN EN 1717
The duct connection facilitates DIN-compliant connection (refer to chapter 3.7).
NOTE:
Waste water backing up due to kinked hoses.
● Risk of water damage.
► Run the hoses to the drain with a downward slope and without kinks and bends.
1.
Shorten the flushing water hose (diameter 12 mm) to the required length.
2.
Fasten the flushing water hose (regeneration water flows out under pressure).
3.
Shorten the overflow hose (diameter 16 mm) to the required length.
4.
Run the overflow hose to the drain with a downward slope.
5.
Make sure there is a free outlet to the drain in accordance with the standard.
6.
Fasten the overflow hose.
If the flow pressure is at least 3 bar, the flushing water hose can be routed up
to 2 m above the floor. It is then not possible to connect the overflow hose.
» This completes the installation.
Protect the product from contamination until it is started up.
► Slide the protective sleeve from the packaging over the product.