Iron / manganese removal
Demanganisation system GENO-mat MN-Z
Order no. 095 153 048-inter Edited by: nkes-mrie G:\BA-153048-INTER_095_GENO-MAT_MN-Z.DOCX
32
3.1.3 Timer settings
For the regeneration/disinfection the corresponding regeneration
tank and the appropriate regeneration agent are required (refer to
3.1 preparation of the regeneration agent).
Flip the cover of the control valve to the side.
Initiate a manual regeneration (see chapter F, point 1.4).
Flip the timer to the right and wait for 10 minutes until limit switch 1
is free (fig. G-1, illustration 1) and the actuator of the control piston
has stopped.
Unplug mains plug.
Open the ball valve on the back of the control valve and suck the
regeneration agent from the connected regeneration tank.
Close the ball valve again after the regeneration agent has been
completely sucked off.
Reconnect mains.
Wait until limit switch 1 is pressed again (fig. G-1, illustration 2)
and the actuator of the control piston has stopped.
Unplug mains plug.
Flush for at least 30 minutes in order to wash out all residues of
the regeneration agent from the filter bed.
Reconnect mains.
The demanganisation system is ready for operation again when
the limit switches 1 and 2 are free (fig. G-1, illustration 3).
Screw cover back on.
Fig. G-1: Rear of timer