39
U
24V
0V
t
PIN 4
E1 0,5 Hz
E1 low
Z1
Z2
The transition of the output signals when changing a cartridge on LUB-D in switched-on
state is shown and described below:
Description:
LUB-D is properly connected to an external controller via the electrical interface and
connected to the power supply.
l
The empty cartridge is detected after a dispense, the output signal of LUB-D is initially
a 0.5Hz square wave signal (empty state signal) (0/+24 V).
l
Z1 indicates the period of removing the empty cartridge. The output signal of LUB-D
now changes from a 0.5Hz square wave signal to a permanent low signal (0V).
l
Z2 indicates the period of screwing on a new, full cartridge. The output signal of LUB-D
now changes from a permanent low signal (0V) to a permanent high signal (+24V). In this
way LUB-D signals to the external controller (PLC) that it is ready for operation again.
l
If the empty state signal has occurred during the execution of the control signal 12
seconds the outstanding strokes are continued after the new cartridge has been screwed
on.
LUB-D does not process any control signals until all errors have been eliminated.
Z1:
Removing the empty cartridge
Z2:
Mounting the new cartridge
Summary of Contents for Lubricus LUB-D Series
Page 1: ...User manual LUB D...