6.6 Active power control with smart meter, or ripple control signal
receiver
Information
The position of export limitation CT or Meter must between the Inverter
& Load and gird and pay attention of the direction.
This series inverter has integrated export limitation functionality. To use this function, you can
connect the Growatt smart meter. For the detailed information, please contact with Growatt.
Fig 6.15
Active power control with a Radio Ripple Control Receiver(RRCR).
Radio ripple con-
trol receiver
Fig 6.16
Router
Public Grid
6.7 GFCI(Standard)
6.7.1 Ground Fault Circuit Interrupt(GFCI)
This inverter includes an integrated residual current device .If the leakage current is over 300mA
and last for more than 300ms,the inverter will report 201 fault and the OLED will display Residual
I High.
The inverter has the function of detecting residual current and protecting the inverter against re-
sidual current. If your inverter must equip a AC breaker which has the function of detecting resid-
ual current ,you must choose a TypeARCD breaker with the rating residual current more than
300mA.