30
Conductor cross
section
Max. cable length
MIC 2000 TL-X
MIC 2500 TL-X
MIC 3000 TL-X
MIC 3300 TL-X
3.3 mm² 12AWG
45m
36m
27m
30m
5.2 mm² 10AWG
73m
58m
44m
48m
6.3 Connecting the second protective conductor
In some installation countries, a second protective conductor is required to prevent a touch current
in
the event of a malfunction in the original protective conductor.For installation countries falling
within the scope of validity of the IEC standard 62109, you must install
the protective conductor
on the AC terminal with a conductor cross-section of at least 10 mm
²
Cu.Or Install a second
protective conductor on the earth terminal with the same cross-section as the original
protective conductor on the AC terminal. This prevents touch current if the original protective
conductor fails.
6.4 Connecting the PV Array (DC input)
6.4.1 Conditions for DC Connection
WARNING
The solar modules connected to the inverter must conform to the Class
A requirements of the IEC 61730 standard.
Please use the same brand male and female PV connectors.
The MIC TL-X series single-phase inverter has only one independent PV input
Notice that the connectors are in paired (male and female connectors). The connectors
for PV arrays and inverters are VP-D4 connectors;