19
Energy stored in this equipment’s DC link capacitors presents a risk of electric
shock. Even after the unit is disconnected from the grid and photovoltaic panels,
high voltages may still exist inside the PV-Inverter. Do not remove the casing
until at least 5 minutes after disconnecting all power sources.
Although designed to meet all safety requirements, some parts and surfaces of
Inverter are still hot during operation. To reduce the risk of injury, do not touch
the heat sink at the back of the PV-Inverter or nearby surfaces while Inverter is
operating.
5.2 Selecting the installation location
This is guidance for installer to choose a suitable installation location, to
avoid potential damages to device and operators.
The installation location must be suitable for the inverter's weight and
dimensions for a long period time.
Select the installation location so that the status display can be easily viewed.
Do not install the inverter on structures constructed of inflammable or
thermolabile materials.
Never install the inverter in environment of little or no air flow, nor dust
environment. That may derate the efficiency of the cooling fan of the
inverter.
The Ingress Protection rate is IP65 which means the inverter can be installed
outdoors and indoors.
The humidity of the installation location should be 0~100% without
condensation.
The installation location must be freely and safely to get at all times.
Vertically installation and make sure the connection of inverter must be
downwards. Never install horizontal and avoids forward and sideways tilt.