E
thernet
P
anel
Hardware EthernetPanel
© 2010 by Grossenbacher Systeme AG DVS 60646 V1.0
21
Pin 3 and 6 (CAN_GND) are both connected internally with the CAN
Ground. Pins 4, 5 and 8 must
not
be connected! The CAN bus driver is fed
internally.
Baud rate and cable lengths
Baud rate
Max. length
20kBit/sec 2500m
25kBit/sec 2000m
50kBit/sec 1000m
100kBit/sec 650m
125kBit/sec 500m
250kBit/sec 250m
500kBit/sec 100m
1Mbit/sec 6m
Shield
Inside: twisted pair cable
Station 1
Station n
bus terminating resistor
DVS 60646-V1.0
Summary of Contents for 50 81 379
Page 38: ...DVS 60646 V1 0...
Page 54: ...DVS 60646 V1 0...