Summary of Contents for 20001401

Page 1: ...LIBRETTO ISTRUZIONI PER L INSTALLAZIONE ACCUMULI SOLARI SILOS 300 M 500 M 1000 M 1500 M 2000 3000 5000 Code 20056870 rev 3 07 15 ...

Page 2: ...9 SILOS 500 M 20055210 SILOS 1000 M 20001401 SILOS 1500 M 20001402 SILOS 2000 20001403 SILOS 3000 20001404 SILOS 5000 20001405 GENERALE Avvertenze generali pag 3 Regole fondamentali di sicurezza 3 Descrizione dell apparecchio 4 Identificazione 4 Struttura 5 Dati tecnici 6 Perdite di carico 6 Dimensioni e peso 7 INSTALLATORE Ricevimento del prodotto pag 8 Movimentazione 9 Locale d installazione del...

Page 3: ...utenzione Riempire sempre l impianto solare con la miscela acqua glicole nella percentuale riportata sul manuale SYLBER di messa in servizio e manutenzione dell impianto Questo libretto é parte integrante dell apparecchio e di conseguenza deve essere conservato con cura e dovrà SEMPRE accompagnare l accumulo anche in caso di sua cessione ad altro proprietario o utente oppure di un trasfe rimento s...

Page 4: ...inserimento di uno scambiatore addizionale Gli accumuli SILOS possono essere equipaggiati con uno specifi co regolatore solare e sono facilmente integrabili in sistemi solari in cui le caldaie o i gruppi termici SYLBER fungono da produttori ausiliari di calore Per il modello SILOS 2000 3000 5000 è disponibile a parte uno scambiatore di calore da montare sulla flangia Gli accumuli solari SILOS sono...

Page 5: ...S 300 M 500 M 1000 M e 1500 M Modelli SILOS 2000 3000 5000 1 Isolamento in poliuretano morbido 100 mm 2 Attacco sfiato mandata Ø 1 1 4F 3 Attacchi mandate ritorni Ø 1 1 2F 4 Pozzetti sonde Ø 1 2 F 7 Serbatoio 9 Flangia per ispezione Struttura SILOS 300 M SILOS 500 M SILOS 1000 M SILOS 1500 M A 215 330 280 390 mm B 595 710 805 850 mm C 975 1090 1335 1310 mm D 1355 1470 1860 1770 mm E 215 330 280 39...

Page 6: ...tino 1 8 1 8 2 6 3 8 m2 Potenza assorbita serpentino 43 45 68 99 kW Produzione di acqua calda riscaldamento 1100 1100 1700 2400 l h Portata necessaria al serpentino 1 9 1 9 2 9 4 2 m3 h Pressione massima di esercizio accumulo 3 bar Temperatura massima di esercizio accumulo 99 C Pressione massima di esercizio serpentino 6 6 6 6 bar Temperatura massima di esercizio serpentino 99 C Perdite di calore ...

Page 7: ... 4 5 PERDITA DI CARICO mbar PORTATA m3 h Ø H Ø H Modelli SILOS 300 M 500 M 1000 M e 1500 M Modelli SILOS 2000 3000 5000 Dimensioni e peso SILOS 300 M SILOS 500 M SILOS 1000 M SILOS 1500 M SILOS 2000 M SILOS 3000 M SILOS 5000 M H Altezza 1635 1775 2190 2165 2480 2720 2870 mm Ø Diametro 700 850 990 1200 1300 1450 1800 mm Peso netto con isolamento 115 140 225 285 345 415 570 kg ...

Page 8: ... dotata di relativa guarnizione il secondo collo protetto anch esso da un sacco in nylon è composto dalla coibentazione in poliuretano dotata dell elegan te rivestimento esterno dagli anelli di rivestimento esterno dei manicotti dal coperchio termoformato dal coperchio copriflan gia le targhette di identificazione e la documentazione Inserito in una busta di plastica posizionata all interno dell i...

Page 9: ... dei bambini il materiale dell imballo in quanto può essere potenziale fonte di pericolo Gli accumuli solari SILOS possono essere installati in tutti i locali in cui non è richiesto un grado di protezione elettrica dell apparecchio superiore a IP X0D Il locale di installazione deve essere asciutto per prevenire la formazione di ruggine Mantenere le distanze minime per la manutenzione e il montaggi...

Page 10: ... della coibenta zione e bloccarla con la apposite cerniere lampo 2 presenti agli estremi Forare la coibentazione in corrispondenza dei fori per gli attac chi ed applicare gli anelli di rivestimento 3 Applicare il coperchio copriflangia 4 Applicare infine la parte superiore 5 della coibentazione e coprirla a sua volta con il coperchio 6 Completato il montaggio applicare la targhetta matricola la ta...

Page 11: ...dell impianto e quello principale del quadro di comando su spento Chiudere i dispositivi di intercettazione dell impianto acqua calda non sanitaria Svuotare l accumulo ovvero il circuito secondario dell accumulo nel caso sia presente il circuito primario ESTERNA La pulizia del rivestimento dell accumulo deve essere effettuata con panni inumiditi con acqua e sapone Nel caso di macchie tenaci inumid...

Page 12: ...struction manual contains important instructions and precautions that must be observed to ensure the trouble free installation and efficient functioning of your SILOS solar storage tank Please accept our renewed thanks for your purchase SYLBER GENERAL Safety precautions page 13 General safety information 13 Product description 14 Identification 14 Design 15 Technical specifications 16 Pressure dro...

Page 13: ...parately purchased anti freeze propylene glycol with water in a percentage varying from 30 to 50 as instructed in the relevant SYLBER installation and maintenance manual Only fill the solar heating system with water and glycol premi xed in the percentages specified in the SYLBER installation and maintenance manual This instruction manual is an integral part of the storage tank It must be kept safe...

Page 14: ...st important technical features of these storage tanks are The tank and coils SILOS 300 m 500 m 1000 m and 1500 M models only are specially designed and shaped for optimum performance in terms of stratification heat exchange and reple nishment times Water fittings are available at different heights permitting diffe rent hot water generators to be used without reducing the strati fication effect CF...

Page 15: ... M 1000 M and 1500 M models SILOS 2000 3000 5000 models 1 Soft polyurethane insulation 100 mm 2 Vent outlet fitting Ø 1 1 4F 3 Outlet return fittings Ø 1 1 2F 4 Probe wells Ø 1 2 F 7 Tank 9 Tank inspection flange Design SILOS 300 M SILOS 500 M SILOS 1000 M SILOS 1500 M A 215 330 280 390 mm B 595 710 805 850 mm C 975 1090 1335 1310 mm D 1355 1470 1860 1770 mm E 215 330 280 390 mm F 815 930 990 1290...

Page 16: ...ace area 1 8 1 8 2 6 3 8 m2 Power absorbed by coil 43 45 68 99 kW Heating hot water production 1100 1100 1700 2400 l h Necessary capacity heat exchanger 1 9 1 9 2 9 4 2 m3 h Maximum working pressure of storage tank 3 bar Maximum working temperature of storage tank 99 C Maximum working pressure of coil 6 6 6 6 bar Maximum working temperature of coil 99 C Heat loss 1 64 2 20 2 97 3 90 4 78 5 88 7 98...

Page 17: ...2000 3000 5000 models Dimensions and weight SILOS 300 M SILOS 500 M SILOS 1000 M SILOS 1500 M SILOS 2000 M SILOS 3000 M SILOS 5000 M H Height 1635 1775 2190 2165 2480 2720 2870 mm Ø Diameter 700 850 990 1200 1300 1450 1800 mm Net weight with insulation 115 140 225 285 345 415 570 kg Heat exchanger coil KIT PRESSURE DROP SILOS 2000 3000 5000 models only PRESSURE DROP mbar FLOW RATE m3 h ...

Page 18: ...counter flange comes ready bolted to the tank s flange and fitted with a seal The second package contains another plastic bag with the elegantly finished polyurethane insulation fitting sleeves for the insulation thermoformed cover flange cover identification plates and documentation The following items are delivered in a plastic bag inside the packaging instruction manual data plate and label wit...

Page 19: ... 1 2 1 1 Handling SILOS 2000 3000 5000 Place of installation Installation in older systems and systems requiring modernisation SILOS 300 M 500 M 1000 M 1500 M Make sure that any lifting equipment is of adequate capacity to lift and move the storage tank Cut the straps 1 to remove the tank from the pallet On SILOS 300 M 500 M 1000 M e 1500 M models the straps are located under the insulation at the...

Page 20: ... tank carefully lining up the fittings with the holes on the inside of the insulation Se cure the insulation in place with the zips 2 at the edges of the two sections Perforate the insulation at the fittings and fit the insulation slee ves 3 Fit the flange cover 4 Finally fit the insulation top panel 5 and cover it with the cover 6 With all the insulation in place apply the serial number plate dat...

Page 21: ...tricity supply to all the devices in the storage tank s water circuit and to any associated boiler OFF at the main switch and at the control panel Close the shut off cocks for the heating water circuit Drain the storage tank or its secondary circuit if a primary circuit is connected EXTERNAL CLEANING Clean the outside of the storage tank s insulation with a soft cloth damped in soapy water To remo...

Page 22: ...22 ...

Page 23: ......

Page 24: ...va di variare le caratteristiche e i dati riportati nel presente fascicolo in qualunque momento e senza preavviso nell intento di migliorare i prodotti Questo fascicolo pertanto non può essere considerato come contratto nei confronti di terzi Code 20056870 rev 3 07 15 ...