background image

OM-BPM-15/30/40G(C,A) (CE) INTERNATIONAL

2.   Put enough water into the pan to cover the bottom to a depth of 1/4 to 1/2 inch 

(6 to 13 mm).  With the pan body in the horizontal position, note how the water 
lies in the pan, to confirm that the pan was leveled properly during installation.

3.  Verify that the rear heat shield is in place.
4.   Following “To Start Pan” instructions for your pan model, begin heating the 

water at a temperature setting of 235°F (113°C). At this setting, heating should 
continue until the water boils.

5.   To shut down the unit, switch the power switch to “OFF”.
6.   Turn the tilting handwheel clockwise to pour out the water and to confirm that 

the pan body can be tilted smoothly from horizontal to vertical. For power tilt 
models, push the UP/DOWN switch to confirm operation of tilting system.

If the unit functions as described above, it is ready for use. If it does not, contact 
your local Engineer (CE).

SETTING THE GAS PRESSURE

1.   During commissioning, a gas pressure check is essential. Connect a suitable 

pressure gauge to the gas manifold to perform this test. The pressure gauge 
should be connected to the test nipple. See photograph above, left.

2.   Turn the gas and electricity mains on.
3.   Light the burners as described above.
4.   Manifold gas pressure should be as noted in the Installation section of this 

manual. If adjustment is necessary, follow steps 5 through 10, below.

5.   Remove the screws which secure the ignition module cover and remove the 

ignition module cover panel. See image above, center.

6.   Remove the governor cap screw on the gas control valve to gain access to the 

screw inside the turret. See image above, right.

7.   The governor is suitable for both natural and propane gas.
8.   Turn the screw inside the turret clockwise to increase the pressure, anti-

clockwise to reduce it. Check the burner pressure again after 15 minutes 
operation, and adjust if necessary.

9.   Disconnect the pressure gauge from the test point. Reseal the test point and 

test for gas soundness.

10.  Replace governor cap screw, and replace control box panel and lid.

INSTALLER

DANGER: FLAMMABLE
WARNING:   DO NOT OVERFILL WITH OIL OR FIRE MAY RESULT!
CAUTION:  THE TEMPERATURE MUST NOT EXCEED 200ºC OR THE HIGH LIMIT 

THERMOSTAT WILL TRIP.

IMPORTANT: THESE APPLIANCES MUST BE INSTALLED BY A COMPETENT PERSON IN 

CONFORMITY WITH THE INSTALLATION AND SERVICING INSTRUCTIONS 

AND NATIONAL REGULATIONS IN FORCE AT THE TIME. PARTICULAR 

ATTENTION MUST BE PAID TO THE FOLLOWING:
I. E. E. REGULATIONS FOR ELECTRICAL INSTALLATIONS
ELECTRICITY AT WORK REGULATIONS
GAS SAFETY (INSTALLATION & USE REGULATIONS
HEALTH AND SAFETY AT WORK ACT
FIRE PRECAUTIONS ACT
LOCAL AND NATIONAL BUILDING REGULATIONS

 

DETAILED RECOMMENDATIONS ARE CONTAINED IN INSTITUTE OF GAS 

ENGINEERS PUBLISHED DOCUMENTS: IGE/UP/1, IGE/UP/2, BS6173 AND 

BS5440.

After installing and commissioning the appliance, the User’s Instructions should be 
handed to the user or purchaser. Ensure that the instructions for lighting, turning 
off, correct use and cleaning are properly understood. Emphasize the location of the 
main gas isolating valve and demonstrate the emergency shut down procedure.

OPERATION

CAUTION:  DO NOT HEAT AN EMPTY PAN FOR MORE THAN FIVE MINUTES AT A  SETTING 

HIGHER THAN 300°F (149°C).  DAMAGE TO THE PAN COULD RESULT.

WARNING:  KEEP THE AREA AROUND BRAISING PAN FREE AND CLEAR OF COMBUSTIBLE 

MATERIALS.

CAUTION:  KEEP FLOORS IN BRAISING PAN WORK AREA CLEAN AND DRY. IF SPILLS 

OCCUR, CLEAN IMMEDIATELY TO AVOID THE DANGER OF SLIPS OR FALLS.

CAUTION:  REPLACE THE HOLE PLUG BEFORE CLEANING OTHERWISE WATER COULD 

ENTER THE ELECTRICAL CONTROL BOX AND DAMAGE THE PARTS.

Classic Control

Advanced Control

OPERATOR CONTROLS
1.  Classic Control (-GC) Models 

a.  Lighted Power ON switch located on the control console. It controls main 

power to the unit.

b.  The temperature knob, located on the control console, is used to set the 

pan temperatures between 175° and 425°F (79° and 218°C).

c.  Heating indicator light is located on the control console, it illuminates 

when the controller calls for the main gas valve to open. If the unit is tilted, 
the call for heat will be interrupted and the light will turn off until the unit 
is returned to the cooking position.

d.  A handwheel controls the worm and gear mechanism that smoothly tilts 

the pan body and holds it in the desired position

2.  Advanced Control (-GA) models

a.  Lighted Power ON switch located on the control console. It controls main 

power to the unit.

b.  Heating indicator light is located on the control console, it illuminates 

when the controller calls for the main gas valve to open. If the unit is tilted, 
the call for heat will be interrupted and the light will turn off until the unit 
is returned to the cooking position.

c.  SET TnnP Mode – Allows the pilot to light but the main burners remain off; 

unit will go into SET TnnP mode at start-up automatically and remain there 
until the user uses one of the LOW TEMP, MANUAL or HIGH TEMP buttons 
to specify the set temperature.

d.  LOW TEMP Button – Used to set operating temperature on of the pan at 

a preset low temperature (default = 175°F/79°C).  Can be pressed at any 
point during operation of the unit to change the set temperature to the 
preset value except when there is an active TIMER enabled.

e.  MANUAL button – Enables the user modify the desired cooking 

temperature of the pan (between 175°F/79°C and 425°F/218°C) using 
the temperature knob and display (default = 212°F/100°C).  The operator 
will press the MANUAL button and set the desired temperature using the 
temperature knob and display.  Once the desired temperature is shown in 
the display, the user may either press the MANUAL button again or wait 
5 seconds and the set temperature will be accepted by the control and 
locked in.  After the set temperature is accepted, it may be changed at any 

Summary of Contents for BMP-30GC

Page 1: ...stainless steel welded into one solid piece with a polished interior and exterior A pouring lip is welded to the front wall The cooking surface is a stainless steel clad plate fitted with welded heat...

Page 2: ...K AREA CLEAN AND DRY IF SPILLS OCCUR CLEAN IMMEDIATELY TO AVOID THE DANGER OF SLIPS OR FALLS WARNING WHEN TILTING BRAISING PAN FOR PRODUCT TRANSFER 1 USE CONTAINER DEEP ENOUGH TO CONTAIN AND MINIMIZE...

Page 3: ...at the top of the Service Log in this manual The unit is strapped to a skid Cut the straps holding the unit on the skid and lift the unit straight up off the skid Shown is a model BPM 40GA with optio...

Page 4: ...t is designed for connection to fixed wiring A suitably rated isolating switch with contact separation of at least three millimeters on both poles must be fitted to the installation The wiring must be...

Page 5: ...2 BS6173 AND BS5440 After installing and commissioning the appliance the User s Instructions should be handed to the user or purchaser Ensure that the instructions for lighting turning off correct use...

Page 6: ...heel clockwise to tilt the pan body or counterclockwise to return the pan body to horizontal 23 complete turns of the handwheel will tilt the body 90 degrees to vertical 2 For Classic Control GC Model...

Page 7: ...ither model will heat operate when the braising pan has been tilted 10 degrees or more from the horizontal CLEANING WARNING KEEP WATER AND SOLUTIONS OUT OF CONTROLS AND ELECTRICAL EQUIPMENT DO NOT USE...

Page 8: ...rd to tilt Authorized Service Rep Only a Gears or foreign materials lubrication and alignment X b Broken tilt or worm gears X Burners will not light User a That the main gas supply valve is open handl...

Page 9: ...sealant as specified above in Note 2 as appropriate after any gas connection has been disturbed 3 Check for correct operation as appropriate see Installation CE Models Gas System Performance Regular S...

Page 10: ...disconnect main power Adjustment is located on the back of the control board Turn adjustment counter clockwise to increase temperature and clockwise to decrease REMOVAL OF HIGH LIMIT THERMOSTAT Turn...

Page 11: ...from burner manifold 3 Replace in reverse order FUSE REPLACEMENT 1 Remove the control cabinet side panel as described in REMOVAL OF CONTROL CABINET PANELS 2 Remove fuse from fuse holder See figure 3 a...

Page 12: ...ER ORIFICE 128158 148412 1 IGNITION TUBE ORIFICE 40 GAL 101622 101665 1 IGNITION TUBE ORIFICE 30 GAL 056932 112603 1 GAS VALVE 160776 160796 Parts List FUEL GAS CONVERSION CALL FACTORY FOR REPLACEMENT...

Page 13: ...ME NUTS 1 4 20 090567 8 2 SCREW TRUSS HEAD 10 32 X 3 8 004173 Parts List COVER COUNTERBALANCE ASSEMBLIES CALL FACTORY FOR REPLACEMENT PARTS 888 994 7636 Parts List MANUAL TILT ASSEMBLY CALL FACTORY FO...

Page 14: ...4 005554 10 1 COUPLING FULL 1 2 NPT 005722 11 1 NIPPLE 1 2 NPT X 10 LONG 005558 12 1 THERMOSTAT HIGH LIMIT 013481 13 1 BRACKET REAR RADIATION HEAT 146145 14 1 COVER IGNITION MODULE 146146 15 2 SCREW R...

Page 15: ...0 012940 7 1 IGNITION TUBE 15 GAL 155722 7 1 IGNITION TUBE 30 GAL 145957 7 1 IGNITION TUBE 40 GAL 145912 8 1 IGNITION TUBE ORIFICE 15 GAL NATURAL GAS CE 101623 8 1 IGNITION TUBE ORIFICE 15 GAL PROPANE...

Page 16: ...D HEAD 34 40 X 3 4 003122 21 2 NUT HEXAGON 4 40 003121 22 2 WASHER 6 INTERNAL TOOTH 013418 23 1 GOUND LUG 119829 23 6 SCREW HEX SLOTTED 069773 24 1 TRANSFORMER CE 50VA 208 230 460V 148899 26 1 TERMINA...

Page 17: ...17 OM BPM 15 30 40G C A CE INTERNATIONAL Wiring Diagram CALL FACTORY FOR REPLACEMENT PARTS 888 994 7636...

Page 18: ...18 OM BPM 15 30 40G C A CE INTERNATIONAL Wiring Diagram STANDING PILOT IGNITION SYSTEM CALL FACTORY FOR REPLACEMENT PARTS 888 994 7636...

Page 19: ...19 OM BPM 15 30 40G C A CE INTERNATIONAL Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed By...

Reviews: