Carbon Monoxide Transmitter Modbus
Installation Manual
May 5, 2017
IN-CMD5B4MOD-01-01 Page 14
40009 +8 Word
R/W
Unsigned 16-bit integer
0x0000 = Buzzer Disable, 0x0001 = Buzzer Enable
40010 +9 Word
R/W
Unsigned 16-bit integer, BUZZER_TRIP = 0 to 0x0030
TRIP = 20 + 10 * (BUZZER_TRIP) = 20 to 500 ppm
40011 +10 MIN
Word
R/W
Unsigned 16-bit integer, BUZZER_DELAY = 0 to 0x000A
DELAY = BUZZER_DELAY = 0 to 10 minutes
40012 +11
Word R/W
Unsigned 16-bit integer, RELAY1_TRIP = 0 to 0x0030
TRIP = 20 + 10 * (RELAY1_TRIP) = 20 to 500 ppm
40013 +12
Word R/W
Unsigned 16-bit integer, RELAY1_HYST = 0 to 0x0012
HYST = 10 + 5 * (RELAY1_HYST) = 10 to 100 ppm
40014 +13 MIN
Word R/W
Unsigned 16-bit integer, RELAY1_DELAY = 0 to 0x000A
DELAY = RELAY1_DELAY = 0 to 10 minutes
40015 +14 Word
R/W
Unsigned 16-bit integer, RELAY2_TRIP = 0 to 0x0030
TRIP = 20 + 10 * (RELAY2_TRIP) = 20 to 500 ppm
40016 +15 Word
R/W
Unsigned 16-bit integer, RELAY2_HYST = 0 to 0x0012
HYST = 10 + 5 * (RELAY2_HYST) = 10 to 100 ppm
40017 +16 MIN
Word
R/W
Unsigned 16-bit integer, RELAY2_DELAY = 0 to 0x000A
DELAY = RELAY2_DELAY = 0 to 10 minutes
40018 +17
Word R/W
Unsigned 16-bit integer
0x0000 = Test Mode Disable, 0x0001 = Test Mode Enable
40019 +18 Word
R/W
Unsigned 16-bit integer, TEST_TIME = 0 to 0x000E
TIME = 1 + (TEST_TIME) = 1 to 15 minutes
40020 +19
Word R/W
Unsigned 16-bit integer
0x0000 = Fault Mode Disable, 0x0001 = Fault Mode Enable
0x0002 = Fault Mode Reset, Revert to Disable
40021 +20
Word R/W
Unsigned 16-bit integer, FAULT_TIME = 0 to 0x0003
TIME = 3 + (FAULT_TIME) = 3 to 6 years
40022 +21 Word
R/W
Unsigned 16-bit integer
0x0000 = Status Display, 0x0001 = CO Value Display
40023 +22 Word
R/W
Unsigned 16-bit integer
0x0000 = Backlight Disable, 0x0001 = Backlight Enable
40024 +23
Word R/W
Unsigned 16-bit integer, OUT_TEST = 0 to 0x0006
OUT = 0(OFF), 1(4mA), 2(8mA), 3(12mA), 4(16mA), 5=6(20mA)
or
OUT = 0(OFF), 1(0V), 2(1V), 3(2V), 4(3V), 5(4V), 6(5V)
or
OUT = 0(OFF), 1(0V), 2(2V), 3(4V), 4(6V), 5(8V), 6(10V)
40025 +24
Word R/W
Unsigned 16-bit integer
0x0000 = ReCal Mode Disable, 0x0001 = ReCal Mode Enable
0x0002 = ReCal Mode Reset, Revert to Enable
40026 +25
Word R/W
Unsigned 16-bit integer, ReCal_TIME = 0 to 0x0002
TIME = 1 + (ReCal_TIME) = 1 to 3 years
40027 +26 Word
R/W
Unsigned 16-bit integer
0 = °C, 1 = °F
40028 +27
°C/°F
Word R/W
Unsigned 16-bit integer, TEMPERATURE_OFFSET = 0 to 0x14
C_OFFSET = TEMPERATURE_OFFSET / 2 - 5 = -5.0 to 5.0 °C
F_OFFSET = TEMPERATURE_OFFSET - 10 = -10 to 10 °F