Carbon Monoxide Transmitter Modbus
Installation Manual
May 5, 2017
IN-CMD5B4MOD-01-01 Page 6
<MENU>
4.
Buzzer
Use the <ROLL> key to scroll through the available options. The buzzer delay may be set from 0 to 10
Del 5Min
minutes in 1 minute increments. Press <SAVE> to save the setting. The factory default is 5 minutes. This
item will not be shown if the buzzer is disabled.
<MENU>
5.
Buzzer
Use the <ROLL> key to toggle the buzzer ON or OFF. This item will not be shown if the buzzer is
Test OFF
disabled.
<MENU>
6.
Relay 1
Use the <ROLL> key to scroll through the available options. The relay 1 alarm trip point may be set from
Trip 50
20 to 500 ppm in 10 ppm increments. Press <SAVE> to save the setting. The factory default is 50 ppm.
This item will not be shown if relay 1 is not installed.
<MENU>
7.
Relay 1
Use the <ROLL> key to scroll through the available options. The relay 1 hysteresis may be set from 10 to
Hyst 10
100 ppm in 5 ppm increments. Press <SAVE> to save the setting. The factory default is 10 ppm. Note that
the maximum value may be limited by the trip point value. This item will not be shown if relay 1 is not
installed.
<MENU>
8.
Relay 1
Use the <ROLL> key to scroll through the available options. The relay 1 delay may be set from 0 to 10
Del 2Min
minutes in 1 minute increments. Press <SAVE> to save the setting. The factory default is 2 minutes. This
item will not be shown if relay 1 is not installed.
<MENU>
9.
Relay 1
Use the <ROLL> key to toggle relay 1 ON or OFF. This item will not be shown if relay 1 is not installed.
Test OFF
<MENU>
10.
Relay 2
Use the <ROLL> key to scroll through the available options. The relay 2 alarm trip point may be set from
Trip 150
20 to 500 ppm in 10 ppm increments. Press <SAVE> to save the setting. The factory default is 150 ppm.
This item will not be shown if relay 2 is not installed.
<MENU>
11.
Relay 2
Use the <ROLL> key to scroll through the available options. The relay 2 hysteresis may be set from 10 to
Hyst 20
100 ppm in 5 ppm increments. Press <SAVE> to save the setting. The factory default is 20 ppm. Note that
the maximum value may be limited by the trip point value. This item will not be shown if relay 2 is not
installed.
<MENU>
12.
Relay 2
Use the <ROLL> key to scroll through the available options. The relay 2 delay may be set from 0 to 10
Del 2Min
minutes in 1 minute increments. Press <SAVE> to save the setting. The factory default is 2 minutes. This
item will not be shown if relay 2 is not installed.
<MENU>
13.
Relay 2
Use the <ROLL> key to toggle relay 2 ON or OFF. This item will not be shown if relay 2 is not installed.
Test OFF
<MENU>
14.
TestMode
Use the <ROLL> key to disable or enable the test mode. The factory default is Disable. When disabled, the
Disable
TEST switch or TEST input will not initiate the test function. When enabled, pressing the TEST switch will