Carbon Monoxide Transmitter Modbus
Installation Manual
May 5, 2017
IN-CMD5B4MOD-01-01 Page 20
0x06 --- Write single register (FAULT_TIME)
Query
Slave address
(0x01 to 0xFF)
0x06
0x00 0x14 0x00
Register
value LSB
CRC
LSB
CRC
MSB
Response
Slave address
(0x01 to 0xFF)
0x06
0x00 0x14 0x00
Register
value LSB
CRC
LSB
CRC
MSB
* Register value = 0x0000 to 0x0003, corresponding to 3 to 6 years, TIME = 3 + (FAULT_TIME)
0x06 --- Write single register (DISPLAY_MODE)
Query
Slave address
(0x01 to 0xFF)
0x06
0x00 0x15 0x00
Register
value LSB
CRC
LSB
CRC
MSB
Response
Slave address
(0x01 to 0xFF)
0x06 0x00 0x15 0x00
Register
value LSB
CRC
LSB
CRC
MSB
* Register value = 0x0000 = status display, 0x0001 = CO value display
0x06 --- Write single register (BACKLIGHT_ENABLE)
Query
Slave address
(0x01 to 0xFF)
0x06
0x00 0x16 0x00
Register
value LSB
CRC
LSB
CRC
MSB
Response
Slave address
(0x01 to 0xFF)
0x06
0x00 0x16 0x00
Register
value LSB
CRC
LSB
CRC
MSB
* Register value = 0x0000 = backlight disable, 0x0001 = backlight enable
0x06 --- Write single register (OUTPUT_TEST)
Query
Slave address
(0x01 to 0xFF)
0x06
0x00 0x17 0x00
Register
value LSB*
CRC
LSB
CRC
MSB
Response
Slave address
(0x01 to 0xFF)
0x06
0x00 0x17 0x00
Register
value LSB*
CRC
LSB
CRC
MSB
* Registers value = 0x0000 to 0x0006, corresponding to the output signal level (depends on output setting)
OUT = 0(OFF), 1(0V), 2(1V), 3(2V), 4(3V), 5(4V), 6(5V) for 0-5 Vdc output
OUT = 0(OFF), 1(0V), 2(2V), 3(4V), 4(6V), 5(8V), 6(10V) for 0-10 Vdc output
OUT = 0(OFF), 1(4mA), 2(8mA), 3(12mA), 4(16mA), 5(20mA), 6(20mA) for 4-20 mA output