Page 9
Use <UP> or <DOWN> to scroll through the available options.
The strobe alarm trip point for CO may be set to OFF or from
20 to 500 ppm in 10 ppm increments. The default is 150 ppm.
The strobe may operate as a CO alarm, a NO
2
alarm or both
depending on the trip point settings. If set to OFF, then the
strobe will not operate as a CO alarm.
Strobe
Enable
Use <UP> or <DOWN> to enable or disable the Strobe LED. When disabled, the
Strobe will not flash if the strobe trip point is exceeded. The strobe will still flash
on startup and will still flash for a fault alarm (if enabled). The factory default is
Enable.
<MENU>
Press to advance to next menu item
9. STROBE
CO Strb
Trip 150
Only if the
strobe
is enabled and the
CO sensor
is installed
10. CO STROBE
TRIP
Use <UP> or <DOWN> to scroll through the available options.
The CO strobe delay may be set from 0 to 10 minutes in 1 minute
increments. The default is 5 minutes.
Use <UP> or <DOWN> to scroll through the available options.
The NO2 strobe delay may be set from 0 to 10 minutes in 1
minute increments. The default is 5 minutes.
Use <UP> or <DOWN> to scroll through the available options.
The strobe alarm trip point for NO
2
may be set to OFF or from 1
to 10 ppm in 1 ppm increments. The default is 2 ppm. The strobe
may operate as a CO alarm, a NO
2
alarm or both depending
on the trip point settings. If set to OFF, then the strobe will not
operate as a NO2 alarm.
CO Strb
Dly 5Min
NO2 Strb
Dly 5Min
NO2 Strb
Trip 2
Only if the
strobe
is enabled, the
CO sensor
is installed and the
CO Strb Trip
is not set to
OFF
Only if the
strobe
is enabled, the
NO
2
sensor
is installed and the
NO
2
Strb Trip
is not set to
OFF
Only if the
strobe
is enabled, the
NO
2
sensor
is installed
11. CO STROBE
DELAY
13. NO
2
STROBE DELAY
12. NO
2
STROBE TRIP
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
Alarm 1
CO
Press the <UP> or <DOWN> to scroll through the available
options. The available options are CO or NO
2
. Alarm1 may be
assigned to either sensor. The default is CO.
Only if
Relay1
installed & only if
2 sensors
are installed
15. ALARM 1
Use <UP> or <DOWN> to toggle the strobe ON or OFF. Press
<MENU> to reset to OFF and advance.
Strobe
Test OFF
Only if the
strobe
is enabled
14. STROBE
TEST
<MENU>
Press to advance to next menu item
IN-GE-GDTXXX-06