Page 12
Use <UP> or <DOWN> to set the NO
2
fault mode timer to
Disable, 1, 2, 3, 4 years or Reset. The factory default is Disable.
When disabled, the device will not sound the buzzer or provide
LCD and status LED indication when the NO
2
sensor life is
exceeded. When set to 1, 2, 3 or 4 years, the fault alarm will
activate to indicate that the NO
2
sensor life is exceeded. If set
to Reset and <MENU> is pressed, then the fault condition for
the NO
2
sensor is cleared, the NO
2
life-time timer is reset and
NO
2
fault mode remains at the previous setting. The timer is
automatically reset if the NO
2
sensor is replaced. If the desired
time has already been exceeded, then it cannot be selected.
Use <UP> or <DOWN> to set the CO fault mode timer to
Disable, 3, 4, 5, 6 years or Reset. The factory default is Disable.
When disabled, the device will not sound the buzzer or provide
LCD and status LED indication when the CO sensor life is
exceeded. When set to 3, 4, 5 or 6 years, the fault alarm will
activate to indicate that the CO sensor life is exceeded. If set to
Reset and <MENU> is pressed, then the fault condition for the
CO sensor is cleared, the CO life-time timer is reset, and CO fault
mode remains at the previous setting. The timer is automatically
reset if the CO sensor is replaced. If the desired time has already
been exceeded, then it cannot be selected.
Only if
CO Sensor
is installed
Only if
NO
2
Sensor
is installed
CO Fault
Disable
TestMode
Time 5
29. CO FAULT
MODE TIMER
30. NO
2
FAULT
MODE TIMER
<MENU>
Press to advance to next menu item
<MENU>
Press to advance to next menu item
Use <UP> or <DOWN> to set the CO recalibration mode timer
to Disable, 1, 2, 3 years or Reset. The default is 1 Year. When
disabled, the device will not sound the buzzer or provide
LCD and status LED indication when the CO sensor requires
recalibration. When set to 1, 2 or 3 years, the Re-Cal alarm will
activate to indicate that the CO sensor requires recalibration. If
set to Reset and <MENU> is pressed, then the Re-Cal condition
for the CO sensor is cleared, the CO Re-Cal timer is reset and
the CO Re-Cal mode remains at the previous setting. The timer
is automatically reset if the CO sensor is replaced. If the desired
time has already been exceeded, then it cannot be selected. If
the CO sensor is calibrated with gas via the User Menu then the
timer will be automatically reset.
Only if
CO Sensor
is installed
CO ReCal
1 Year
31. CO RECAL
MODE