Greystone Energy Systems GDT Series Installation Instructions Manual Download Page 2

Page  2

The enclosure has a hinged cover with a latch. Open the 

cover by pulling slightly on the latch on the right side of 

the enclosure. At the same time pulling on the cover.

Make wiring connections as per the “Wiring” illustrations. 

See Figure 9.

Swing door closed until securely latched. For added 

security, 2 screws are provided that may be installed in 

the integrated screw tabs. See Figure 5.

WIRING

Deactivate the 24 Vac/dc power supply until all connections are made to the device to prevent electrical 

shock or equipment damage. Follow proper electrostatic discharge (ESD) handling procedures when 

installing the device or equipment damage may occur. Use 14-22 AWG shielded wire for all connections 

and do not locate the device wires in the same conduit with wiring used to supply inductive loads such 

as motors. Pull enough wire into the enclosure to reach the terminal blocks and complete the wiring 

connection according to the wiring diagram. Make all connections in accordance with national and local 

codes.

Connect the plus DC or the AC voltage hot side to the PWR terminal and the power supply common is 

connected to the COM terminal. The device is reverse voltage protected and will not operate if connected 

backwards. It has a half-wave power supply so the supply common is the same as the signal common. Use 

caution when wiring multiple devices or when grounding the secondary of a transformer to ensure that 

the circuit ground point is the same on all devices and the controller.

The sensor can be ordered with four output options. Analog options include 4-20 mA active output or 

voltage output configurable as 0-5 Vdc or 0-10 Vdc. Network options include BACnet® or Modbus.

The analog outputs are available on the CO, TEMP and 

NO

2

 terminals. The signal type may be ordered as either 

voltage or 4-20 mA active outputs. The voltage model 

is selectable for either 0-5 or 0-10 Vdc via the menu (the 

factory default is 0-5 Vdc). The current outputs operate 

in the active mode and do not require a loop power 

supply. This means that the signal current is generated 

by the sensor and the outputs must not be connected 

to a powered input or device damage will result. Check 

the controller Analog Inputs (AI) to determine proper 

connection before applying power. Both current and 

voltage output signals are referenced to the COM terminal. 

The analog output signals are typically connected directly 

to the Building Automation System (BAS) and used as 

control parameters. See Figure 6.

Figure 5

Figure 6

Typical wiring for 24 Vdc power from controller

Typical wiring for 24 Vac power from controller

Controller

Controller

24 Vac Transformer

PWR

COM

CO

TEMP

NO2

PWR

COM

CO

TEMP

NO2

+24 Vdc

COMMON

Analog Input

Analog Input

Analog Input

COMMON

Analog Input

Analog Input

Analog Input

24 Vac

COMMON

-

+

STATUS STROBE ALARM

UP

TEST

RL1

RL2

DOWN

MENU

PWR CO

M

TEST

B+ A- SHLD

CO TEMP NO2

RP RC CSLP SCLM SD

AP

SDA

M

RT+ RT-

NC1 COM1 NO1 NC2 COM2 NO2

IN-GE-GDTXXX-06

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for GDT Series

Page 1: ...les that are provided on each corner of the enclosure using screws not provided Ensure the sensor pods are pointing downwards as shown in Figure 1 The enclosure offers two entry points for wiring one on top and one on bottom see Figure 2 for locations The enclosure includes one rubber grommet installed in the bottom wiring hole Dependingontheinstallationwiringcanberouted through top or bottom hole...

Page 2: ...the circuit ground point is the same on all devices and the controller The sensor can be ordered with four output options Analog options include 4 20 mA active output or voltage output configurable as 0 5 Vdc or 0 10 Vdc Network options include BACnet or Modbus The analog outputs are available on the CO TEMP and NO2 terminals The signal type may be ordered as either voltage or 4 20 mA active outpu...

Page 3: ...on The maximum daisy chain length segment depends on transmission speed baud rate wire size and number of nodes If communication is slow or unreliable it may be necessary to wire two daisy chains to the controller with a repeater for each segment The toxic gas sensor may have one or two optional relays installed The relays are Form C type with both a normally open NO and a normally closed NC conta...

Page 4: ...15200 Network Address if applicable 0 255 CO sensor range if applicable 0 100 0 150 0 300 0 400 or 0 500 Temperature sensor range if applicable 20 to 50 C 0 to 50 C 4 to 122 F 32 to 122 F After the above display the alarm buzzer will beep twice if applicable The start up mode will continue with a one minute countdown During the warm up mode the alarms will be set to off the Status LED will flash g...

Page 5: ...e LED OFF OFF Flashing Flashing Alarm LED OFF OFF RED RED Buzzer OFF OFF Beep Every 15 seconds Short every 10 minutes Short every 10 minutes ON Short ON Long CO xxx ppm Alarm1 CO xxx Alarm2 NO2 xx x CO xxx ppm When a buzzer alarm condition occurs the buzzer alarm status will be displayed alternately with the normal display If more than one alarm occurs then they will alternate every 2 seconds with...

Page 6: ...be LED operates independently of Alarm1 and Alarm2 and can be disabled via the menu If enabled and the device is in Alarm mode pressing the TEST switch will have no impact on Strobe MANUAL ALARM RESET In this case the alarms will activate the same way as described above but will not automatically reset to Normal Mode when the CO level drops below the trip level hysteresis value In order to reset t...

Page 7: ...ON SETUP MENU The device has several parameters that can be configured locally via the Setup menu using the keypad and LCD All parameters default to typical values but the installer may want to change some values In some cases such as the device network address the installer MUST change the settings before operation Any changes made are saved in non volatile memory and are restored in case of a po...

Page 8: ...m 3 BUZZER CO Buzz Dly 5Min Press the UP or DOWN keys to scroll through the available options The CO buzzer delay may be set from 0 to 10 minutes in 1 minutes increments Is only available if the CO Buzzer Trip is enabled not set to OFF The default is 5 minutes NO2 Buzz Trip 2 NO2 Buzz Dly 5Min Buzzer Test OFF Press the UP or DOWN keys to scroll through the available options The NO2 buzzer delay ma...

Page 9: ...O2 may be set to OFF or from 1 to 10 ppm in 1 ppm increments The default is 2 ppm The strobe may operate as a CO alarm a NO2 alarm or both depending on the trip point settings If set to OFF then the strobe will not operate as a NO2 alarm CO Strb Dly 5Min NO2 Strb Dly 5Min NO2 Strb Trip 2 Only if the strobe is enabled the CO sensor is installed and the CO Strb Trip is not set to OFF Only if the str...

Page 10: ...correct Reverse operation means the relay is normally energized and will de energize on an alarm condition the NO NC PCB designations are reversed Reverse operation can be used for Fail Safe operation as the relay will change state on power loss The default is Direct Press the UP or DOWN to toggle Relay1 ON or OFF to test the relay operation 18 ALARM 1 DELAY 19 RELAY OPERATION 20 RELAY TEST MENU P...

Page 11: ...ration can be used for Fail Safe operation as the relay will change state on power loss The default is Direct Use UP or DOWN to toggle relay2 ON or OFF to test the relay operation Press MENU to reset to OFF Use UP or DOWN to disable or enable the test mode The default is Disable When disabled the front panel TEST switch or TEST input will not initiate the test function When enabled pressing the TE...

Page 12: ...t mode remains at the previous setting The timer is automatically reset if the CO sensor is replaced If the desired time has already been exceeded then it cannot be selected Only if CO Sensor is installed Only if NO2 Sensor is installed CO Fault Disable TestMode Time 5 29 CO FAULT MODE TIMER 30 NO2 FAULT MODE TIMER MENU Press to advance to next menu item MENU Press to advance to next menu item Use...

Page 13: ...o 1 2 or 3 years the Re Cal alarm will activate to indicate that the NO2 sensor requires recalibration If set to Reset and MENU is pressed then the Re Cal condition for the NO2 sensor is cleared the NO2 Re Cal timer is reset and the NO2 Re Cal mode remains at the previous setting The timer automatically resets if the NO2 sensor is replaced If the desired time has already been exceeded then it cann...

Page 14: ... are displayed If set to Status the ppm values will not be displayed only the device operating status If set to None there will not be any LCD display information in Normal mode the LCD will still work for menu operation The default and available options depend on the installed sensors For example if the device only has a CO sensor then CO ppm is the default and the only other options available wi...

Page 15: ...tem MENU Press to advance to next menu item MENU Press to advance to next menu item Only if CO Sensor is installed This item allows zero calibration of the CO sensor Ensure the sensor is in clean air Press and hold the UP key for 3 seconds to initiate the calibration process When the calibration is complete the display will indicate DONE Then press MENU to advance to the next selection A CO Zero C...

Page 16: ...nted every time this step is performed The NO2 Re Cal timer is reset whenever this step is performed NO2 Zero Cal GO NO2 10 Cal GO NO2 Zero Cal DONE NO2 10 Cal DONE 48 ZERO CALIBRATION 49 SPAN CALIBRATION MENU Press to advance to next menu item then then Only if NO2 Sensor is installed This item allows offset calibration of the temperature sensor Use UP or DOWN to add an offset to the temperature ...

Page 17: ...c 2 line x 8 characters 35mm W x 15mm H 1 4 x 0 6 Backlight Enable or disable via menu User Interface Silence Test button Bi color status LED Red LED Alarm indicator White high intensity LED strobe optional TEMPERATURE SIGNAL OPTIONAL Type Thermistor or RTD Accuracy Thermistors 0 2 C 0 36 F 25 C 77 F Platinum RTD s 0 3 C 0 54 F 0 C 32 F Nickel RTD s 0 4 C 0 72 F 0 C 32 F Output 2 Wire Resistive Ty...

Page 18: ...Modbus setup guide downloads are available online BACnet PROTOCOL https downloads greystoneenergy com SG SG GDTXXXBAC 003 pdf MODBUS PROTOCOL https downloads greystoneenergy com SG SG GDTXXXMOD 001 pdf DIMENSIONS 54 5 mm 2 15 160 00 mm 6 29 184 00 mm 7 24 170 00 mm 6 69 32 25 mm 1 26 76 2 mm 3 00 52 0 mm 2 05 82 5 mm 3 25 69 8 mm 2 75 32 25 mm 1 26 IN GE GDTXXX 06 Copyright Greystone Energy System...

Reviews: