CDD4 Duct Carbon Dioxide Transmitter                                               

Installation Manual 

 

 

May 27, 2013

                         

5

 

This item is omitted if the 2000 ppm sensor is installed 

9. 

   Calibrat 

This item is used for 0 ppm gas calibration and is explained in the 

Calibration

 section. 

        

0 PPM 

 

<MENU> 

 

10.    

Calibrat 

This item is used for 1000 ppm gas calibration and is explained in the 

Calibration

 section. 

     1000 PPM 

 

<MENU> 

 

This item is omitted if the 2000 ppm sensor is installed 

11.    

Calibrat 

This item is used for 20,000 ppm gas calibration and is explained in the 

Calibration

 section. 

      20000 PPM 

 

<MENU> 

 

12.

 BackLite 

Use the <ROLL> key to enable or disable the LCD backlight. When enabled the backlight is always on, 

       Enable 

when disabled it never lights. Press the <SAVE> key to save the setting. The factory default is Enable. 

 

<MENU> 

 

13.

  Menu 

Press <SAVE> to exit the menu and return to normal operation or <MENU> to repeat the menu. 

        Exit 

 

 

 

 

 

General Specifications 

Power Supply . . . . . . . . . . . . .  20 

 28 Vac/dc (non-isolated half-wave rectified) 

Consumption . . . . . . . . . . . . . . 100 mA max @ 24 Vdc, 185 ma max @ 24 Vac (with all options) 

Output Signals . . . . . . . . . . . .  4-20 mA active (sourcing), 0-5 Vdc or 0-10 Vdc (field selectable) 

Output Drive Capability . . . . .  550 ohms maximum for current output, 5 Kohm min for voltage output 

Output Resolution . . . . . . . . . . 10 bit PWM 

Input Voltage Effect . . . . . . . .  Negligible over specified operating range 

Protection Circuitry . . . . . . . . . Reverse voltage protected, overvoltage protected 

Operating Conditions . . . . . . .  0-50 

C (32-122 

F), 0-95 %RH non-condensing 

Wiring Connections . . . . . . . .  Screw terminal block (14 to 22 AWG) 

Enclosure . . . . . . . . . . . . . . . . 

5.7”w x 3.95”h x 2.5”d (145 x 100 x 63 mm)

 

Duct Probe . . . . . . . . . . . . . . . 

7” (177 mm) long x 1” (25.4 mm) diameter

 

 

CO2 Signal 

Measurement Type . . . . . . . . . Non-Dispersive Infrared (NDIR), diffusion sampling 

Measurement Range . . . . . . . . 0-2000 ppm (CDD4A) or 0-20,000 ppm (CDD4B), programmable span 

Standard Accuracy . . . . . . . . . 

 30 ppm + 3% of reading (CDD4A with Auto Cal) 

 

 75 ppm or 10% of reading (whichever is greater) (CDD4B with dual-channel sensor) 

Temperature Dependence . . . . 0.2 %FS per 

Stability . . . . . . . . . . . . . . . . . . < 2 %FS over life of sensor (15 years typical) (CDD4A) 

 

< 5 %FS or <10% reading annual (CDD4B) 

Pressure Dependence . . . . . . .  0.135 % of reading per mm Hg 

Altitude Correction . . . . . . . . . Programmable from 0-5000 ft via keypad 

Response Time . . . . . . . . . . . .  < 2 minutes for 90 % step change typical 

Warm-up Time . . . . . . . . . . . .  < 2 minutes

 

 

DISC

ONTINUED

Summary of Contents for CDD4

Page 1: ...ht section of duct at least five feet from corners and other items that may cause disturbances in the air flow Avoid areas where the detector is exposed to vibrations or rapid temperature changes The duct CO2 transmitter principal of operation is based on the Venturi effect of the probe that extends into the HVAC duct Air flowing through the duct is forced into the vent holes on one side of the pr...

Page 2: ...d the controller The analog output is available on the CO2 terminal This signal is switch selectable for either voltage or 4 20 mA active output In voltage mode the output is selectable for either 0 5 or 0 10 Vdc via the menu the factory default is 0 5 Vdc The current output operates in the active mode and does not require a loop power supply This means that the signal current is generated by the ...

Page 3: ...cover of the unit to be calibrated to expose the gas sensor chamber The tubing from the gas bottle can be connected to either port on the chamber after the plastic cap is removed Gently remove one cap and connect the tubing note that strong shock or vibration can affect calibration Ensure the device has been operating normally for at least five minutes before applying gas Turn the valve knob on th...

Page 4: ...tem is omitted if the 20 000 ppm dual channel sensor is installed 3 Auto Cal Automatic Cal Mode default is ON to correct CO2 sensor drift to better than 10 ppm per year Change ON with the ROLL key and save using SAVE ON is recommended for applications where the CO2 level will be close to normal 400 ppm at least once per day If a building is occupied 24 hours and the CO2 level is fairly constant th...

Page 5: ...24 Vac with all options Output Signals 4 20 mA active sourcing 0 5 Vdc or 0 10 Vdc field selectable Output Drive Capability 550 ohms maximum for current output 5 Kohm min for voltage output Output Resolution 10 bit PWM Input Voltage Effect Negligible over specified operating range Protection Circuitry Reverse voltage protected overvoltage protected Operating Conditions 0 50 C 32 122 F 0 95 RH non ...

Page 6: ...x 8 characters Backlight Enable or disable via keypad Optional Temperature Signal Sensing Element Various RTDs and thermistors available as 2 wire resistance output Optional Relay Output Contact Ratings Form A contact N O 2 Amps 140 Vac 2 Amps 30 Vdc Relay Trip Point Programmable via keypad Relay Hysteresis Programmable via keypad D I S C O N T I N U E D ...