CDD4 Duct Carbon Dioxide Transmitter                                               

Installation Manual 

 

 

May 27, 2013

                         

6

 

LCD Display

  

Resolution . . . . . . . . . . . . . . . . 1 ppm CO2 

Size . . . . . . . . . . . . . . . . . . . . . 

1.4” w x 0.6” h (35 x 15 mm) alpha

-numeric 2 line x 8 characters 

Backlight . . . . . . . . . . . . . . . .   Enable or disable via keypad 

 

Optional Temperature Signal 

Sensing Element . . . . . . . . . . . Various RTDs and thermistors available as 2-wire resistance output 

 

Optional Relay Output 

Contact Ratings . . . . . . . . . . .  Form A contact (N.O.), 2 Amps @ 140 Vac, 2 Amps @ 30 Vdc 

Relay Trip Point . . . . . . . . . . .  Programmable via keypad 

Relay Hysteresis . . . . . . . . . . . Programmable via keypad 

 

 

 

 

DISC

ONTINUED

Summary of Contents for CDD4

Page 1: ...ht section of duct at least five feet from corners and other items that may cause disturbances in the air flow Avoid areas where the detector is exposed to vibrations or rapid temperature changes The duct CO2 transmitter principal of operation is based on the Venturi effect of the probe that extends into the HVAC duct Air flowing through the duct is forced into the vent holes on one side of the pr...

Page 2: ...d the controller The analog output is available on the CO2 terminal This signal is switch selectable for either voltage or 4 20 mA active output In voltage mode the output is selectable for either 0 5 or 0 10 Vdc via the menu the factory default is 0 5 Vdc The current output operates in the active mode and does not require a loop power supply This means that the signal current is generated by the ...

Page 3: ...cover of the unit to be calibrated to expose the gas sensor chamber The tubing from the gas bottle can be connected to either port on the chamber after the plastic cap is removed Gently remove one cap and connect the tubing note that strong shock or vibration can affect calibration Ensure the device has been operating normally for at least five minutes before applying gas Turn the valve knob on th...

Page 4: ...tem is omitted if the 20 000 ppm dual channel sensor is installed 3 Auto Cal Automatic Cal Mode default is ON to correct CO2 sensor drift to better than 10 ppm per year Change ON with the ROLL key and save using SAVE ON is recommended for applications where the CO2 level will be close to normal 400 ppm at least once per day If a building is occupied 24 hours and the CO2 level is fairly constant th...

Page 5: ...24 Vac with all options Output Signals 4 20 mA active sourcing 0 5 Vdc or 0 10 Vdc field selectable Output Drive Capability 550 ohms maximum for current output 5 Kohm min for voltage output Output Resolution 10 bit PWM Input Voltage Effect Negligible over specified operating range Protection Circuitry Reverse voltage protected overvoltage protected Operating Conditions 0 50 C 32 122 F 0 95 RH non ...

Page 6: ...x 8 characters Backlight Enable or disable via keypad Optional Temperature Signal Sensing Element Various RTDs and thermistors available as 2 wire resistance output Optional Relay Output Contact Ratings Form A contact N O 2 Amps 140 Vac 2 Amps 30 Vdc Relay Trip Point Programmable via keypad Relay Hysteresis Programmable via keypad D I S C O N T I N U E D ...