CDD4 Duct Carbon Dioxide Transmitter                                               

Installation Manual 

 

 

May 27, 2013

                         

3

 

Start-up 

Verify the device is properly wired and connections are 

tight. Ensure the V/I switch is set for the correct signal 

type. Apply power and the LCD will indicate the software 

version number, the output signal type, the relay setpoint 

(if installed), the CO2 measurement range and then the 

sensor will begin reading the CO2 level, output the correct 

analog signal and display the value on the LCD. 

 

Output

 

The CO2 output is scaled such that 4-20 mA (or 0-5/0-10 

Vdc) equals 0 to Out_High. Depending on the model, the 

factory default is either 0-2000 ppm or 0-20,000 ppm. 

Out_High can be changed in the Setup Menu  and the 

output is scaled accordingly. If using voltage output type, 

the default is 0-5 Vdc (0-10 can be selected in the menu). 

 

Operation

 

The output signal is available on the 

CO2

 terminal and is 

connected to the BAS analog input which reads the signal 

and calculates the CO2 ppm value using correct scaling for 

the  range and signal type. This CO2 value is  used to 

control output ventilation devices or initiate alarms. The 

CO2 value is also displayed locally on the optional LCD. 

 

If a relay is installed it can control a small fan or alarm by 

setting the trip value and hysteresis to appropriate values. 

 

If a  temperature sensor is installed it will be wired to an 

analog input of the BAS  that is set for the specific 

resistance type. This could be a 10 K

 thermistor, a 1000 

ohm RTD or other sensor values. The BAS reads the 

resistance signal and converts it to a temperature value. 

 

Calibration 

Calibration with gas requires a field calibration kit with 

pressure regulator, necessary tubing and appropriate 

bottles of CO2 gas. Note that the procedure depends on the 

device model. The standard model requires only a single 

point 1000 ppm calibration to meet specified accuracy due 

to the Automatic Calibration mode and other technology 

incorporated into the CDD4A model. 

 

The CDD4B dual-channel sensor with extended range 

requires a 3-point calibration with 0, 1000 and 20,000 ppm 

gas (in order). 

 

0 PPM Calibration (For the CDD4B model only) 

Turn the regulator knob off and attach it to the Nitrogen 

gas bottle and hand tighten. Remove the cover of the unit 

to be calibrated to expose the gas sensor chamber. The 

tubing from the gas bottle can be connected to either port 

on the chamber after the plastic cap is removed. Gently 

remove one cap and connect the tubing, note that strong 

shock or vibration can affect calibration. 

 

Ensure the device has been operating normally for at least 

five minutes before applying gas. Turn the valve knob on 

the regulator to start the gas flow. The regulator will 

restrict the flow rate to the specified 100 ml/min. After a 

brief period the gas will flow into the chamber. Wait 1 to 2 

minutes until the CO2 stabilizes. 

 

Enter the Setup menu and use the <MENU> key to 

advance to 

Calibrat 0 PPM

. Press and hold the <SAVE> 

key for 2 seconds and the display will change to 

Waiting 

Calibrat 

then to 

Waiting 5 minute

  to indicate that the 

process of setting the internal calibration is taking place. 

 

This takes  about 5 minutes while  the LCD counts  down. 

Do not disturb the unit or the gas flow. When complete the 

unit will display  the ppm value and 

Cal  Done

.

 

Press 

<SAVE> to resume normal operation and shut the gas off. 

 

1000 PPM Calibration (For all CDD models) 

Connect the 1000 ppm CO2 gas bottle and apply the gas as 

before. The CO2 reading on the LCD will begin to 

approach 1000 ppm. Wait 1 to 2 minutes until the CO2 

reading stabilizes. 

 

Enter the Setup menu and use the <MENU>  key to 

advance to 

Calibrat 1000 PPM

. Press and hold the 

<SAVE> key for 2 seconds and the display will change to 

Waiting Calibrat 

then to 

Waiting 5 minute

  to indicate 

that the device is calibrating. Again, this process takes 

about 5 minutes. When calibration is complete the unit will 

display the ppm value and 

Cal Done

.

 

Press the <SAVE> 

key to return to normal operation and shut the gas off. 

 

20,000 PPM Calibration (For the CDD4B model only) 

Connect the 20,000 ppm CO2 and apply the gas as before. 

The LCD will begin to approach 20,000 ppm. Wait 1 to 2 

minutes until the CO2 reading stabilizes. 

 

Enter the Setup menu and use the <MENU> key to 

advance to 

Calibrat 20,000 PPM

. Press and hold the 

<SAVE> key for 2 seconds and the display will change to 

Waiting Calibrat 

then to 

Waiting 5 minute

 

Again, wait 5 minute and when calibration is complete the 

unit will display  the ppm value and 

Cal Done

.

 

Press 

<SAVE> to resume normal operation and shut the gas off. 

 

Disconnect the tubing and replace the cap on the sensor 

chamber as calibration is complete. 

 

  

 

DISC

ONTINUED

Summary of Contents for CDD4

Page 1: ...ht section of duct at least five feet from corners and other items that may cause disturbances in the air flow Avoid areas where the detector is exposed to vibrations or rapid temperature changes The duct CO2 transmitter principal of operation is based on the Venturi effect of the probe that extends into the HVAC duct Air flowing through the duct is forced into the vent holes on one side of the pr...

Page 2: ...d the controller The analog output is available on the CO2 terminal This signal is switch selectable for either voltage or 4 20 mA active output In voltage mode the output is selectable for either 0 5 or 0 10 Vdc via the menu the factory default is 0 5 Vdc The current output operates in the active mode and does not require a loop power supply This means that the signal current is generated by the ...

Page 3: ...cover of the unit to be calibrated to expose the gas sensor chamber The tubing from the gas bottle can be connected to either port on the chamber after the plastic cap is removed Gently remove one cap and connect the tubing note that strong shock or vibration can affect calibration Ensure the device has been operating normally for at least five minutes before applying gas Turn the valve knob on th...

Page 4: ...tem is omitted if the 20 000 ppm dual channel sensor is installed 3 Auto Cal Automatic Cal Mode default is ON to correct CO2 sensor drift to better than 10 ppm per year Change ON with the ROLL key and save using SAVE ON is recommended for applications where the CO2 level will be close to normal 400 ppm at least once per day If a building is occupied 24 hours and the CO2 level is fairly constant th...

Page 5: ...24 Vac with all options Output Signals 4 20 mA active sourcing 0 5 Vdc or 0 10 Vdc field selectable Output Drive Capability 550 ohms maximum for current output 5 Kohm min for voltage output Output Resolution 10 bit PWM Input Voltage Effect Negligible over specified operating range Protection Circuitry Reverse voltage protected overvoltage protected Operating Conditions 0 50 C 32 122 F 0 95 RH non ...

Page 6: ...x 8 characters Backlight Enable or disable via keypad Optional Temperature Signal Sensing Element Various RTDs and thermistors available as 2 wire resistance output Optional Relay Output Contact Ratings Form A contact N O 2 Amps 140 Vac 2 Amps 30 Vdc Relay Trip Point Programmable via keypad Relay Hysteresis Programmable via keypad D I S C O N T I N U E D ...

Reviews: