OCF 5.0 Open Channel Flow Monitor
CALIBRATION
Press
to
Calibration
and
to enter. Use
or
to position
before each
menu item and
to enter. When settings are completed press
to store and
return to the Calibration menu.
Min Range
Distance from the sensor face to highest expected level.
Max Range
Distance from sensor to Zero level.
MaxVol
For Volume and HRT mode only. Enter the maximum volume of
the vertical or horizontal tank.
Damping
Minimum damping allows fast response to level changes.
Increasing damping slows the OCF 5.0's response to level changes
and is ideal to smooth the display and outputs in turbulent
conditions. Damping value is shown in percent (0-99%). Some
experimentation may be required to select the optimum damping
value. A value of 1% is recommended for most applications and for
fast level changes (up to ½ inch/sec - 13 mm/sec).
LOE Time
Press
and
or
to change the number of seconds without
receiving an echo before the OCF 5.0 displays ECHO LOSS, and
Control relays change state as calibrated under Relay Parameters.
Factory default is 30 seconds and is recommended for most
applications, Minimum is 1 second and maximum is 99 seconds.
Press
to return to Menu Selections.
Summary of Contents for OCF 5.0
Page 2: ...Note This page has been left blank intentionally ...
Page 5: ...Page 5 OCF 5 0 Open Channel Flow Monitor CONNECTIONS ...
Page 7: ...Page 7 OCF 5 0 Open Channel Flow Monitor CALIBRATION MENU ...
Page 8: ...Page 8 OCF 5 0 Open Channel Flow Monitor ICONS ...
Page 14: ...Page 14 OCF 5 0 Open Channel Flow Monitor CHANNEL SETUP ...
Page 20: ...Page 20 OCF 5 0 Open Channel Flow Monitor SENSOR MOUNTING METHODS ...
Page 33: ...Page 33 OCF 5 0 Open Channel Flow Monitor EXTENDED SENSOR CABLE INSTALLATION IN MANHOLE ...
Page 35: ...Page 35 OCF 5 0 Open Channel Flow Monitor ...
Page 41: ......