RELAY PARAMETERS
Each relay can be individually calibrated. Press
È
to
R Function
and
Æ
to select:
Off
Æ
Pulse
Æ
Flow
Æ
Velocity
Æ
Level
.
Off
mode means the relay will not be energized
Pulse
Press
È
and set digits to the flow volume increment required between relay pulses. Use
this feature for remote samplers, chlorinators or totalizers. Maximum pulse setting is
999,999. Minimum time between pulses is 1 second and pulse duration is 350
milliseconds. Selection of
Level
mode disables this function.
Flow
Press
È
to select flow mode for the relay, then
R1on
. Use
È
and
Ç
to set the On flow
rate to energize the relay.
R1Off
use
È
and
Ç
to set the Off set point. Selection of
Level
mode will disable this
function.
Velocity
Press
È
to select velocity mode for the relay, then
R1on
. Use
È
and
Ç
to set the On
flow velocity to energize the relay.
R1Off
use
È
and
Ç
to set the Off flow velocity. Selection of
Level
mode will
disable this function.
Level
Press
È
to select level mode for the relay, then
R1on
. Use
È
and
Ç
to set the On level
to energize the relay.
R1Off
Use
È
and
Ç
to set the Off level.
R1 LOE
. Press
Æ
to select
Off
Æ
On
Æ
Hold
. In a loss of echo condition the relay
will turn off (de-energize), on (energize) or hold its current state. Each relay can be
individually configured. Press
È
.
To calibrate a relay in level mode for echo loss only, set the relay On and Off points to
exactly the same value, then set
LOE
to On mode. The relay will now energize only
when a level echo loss condition occurs.
Press
È
to
Store? Yes
and
Æ
to
Yes
. Press
Ç
or
È
to save your Relay settings.
Manual Series A.10
AVFM-II Area-Velocity Flow Meter
Page 14
CALIBRATION
SPECIAL FUNCTION
RELAY PARAMETERS
Pulse
R1 Function Off
R1on 0.00 ft3
Flow
R1 on 0.00 ft3/s
R1 OFF 0.00 ft3/s
R1 LOE Off
On
Hold
Velocity
Level
Flow
Velocity
R1 on 0.00 ft
R1 OFF 0.00 ft
Pulse
R2 Function Off
Level