2.4.2 Adjust the waveform
Device adopts the traveling wave method to do fault locating.
Through VOP menu to set and adjust wave velocity. Refer Fig.2.6.
Steps:
Chick the VOP menu and choose different waveform velocity or directly to adjust the velocity to a suitable value.
Cross linked(XLPE): Cross linked polyethylene cable,170m/us
Oil paper: Impregnated paper insulated cable,160m/us
Plastic: Plastic cable,201m/us
Robber: Robber cable,220m/us
Use the VOP + & VOP - button to adjust the velocity. Under this interface,if click VOP + or VOP - button,the sub-menu can’t automatically
disappear. Click VOP button or other screen position, the sub-menu will automatically disappear.
Fig.2.5 Range chosen interface
Fig.2.6 Waveform velocity adjustment