background image

Page 12

  6. TROUBLESHOOTING

  7. MAINTENANCE OF THE VENTILATION SYSTEM (PH, PE, SOLACE, DH & SS SERIES)

ROUTINE MAINTENANCE
SEVEN-STEP MAINTENANCE 

SCHEDULE

With routine preventative maintenance, 

you can avoid unnecessary problems, 

ensure the effectiveness of your HRV, 

and prolong its life. For additional 

specific instructions, refer to your HRV 

operating manual or ask the contractor 

who installed or services the HRV to 

demonstrate the proper maintenance 

procedures.

 

 

 WARNING:

  

BE SURE TO DISCONNECT THE 

ELECTRICAL POWER BEFORE 

SERVICING YOUR SYSTEM

1.

 Clean or replace air filters. Filters, 

which are located within the HRV 

should be cleaned every two to three 

months. Filters should be vacuumed 

first, then washed with a mild soap 

and water. Most washable filters will 

last several years before needing to 

be replaced.

2.

 Clean the exterior intake and 

exhaust vents of obstructions.Check 

the outside vents regularly to ensure 

that the screen openings are not 

obstructed by grass, bushes, leaves, 

snow or other debris.

3

. Clean and inspect the heat-exchange 

core and aluminum louvers (

Ref. Fig. 

17.1 for proper orientation of louvers

). 

Twice a year and clean it as required 

(consult your owner’s manual 

for instructions on inspecting and 

cleaning the core). A build-up of dust 

and dirt can restrict airflow and reduce 

the efficiency of your HRV/ERV. After 

inspection and cleaning, make sure the 

core is replaced right-side-up.

4.

 Clean the condensate drain and pan. 

Twice a year, check the condensate 

drain and tubing to ensure that 

they are open and free-flowing. 

The tubing can be disconnected for 

cleaning. The condensate drain must 

have a “trap” in the tubing that traps 

a quantity of water – to prevent air 

from entering the HRV/ERV via this 

tubing

5.

 Service the fans. The fans on the 

HRV/ERV’s are designed to operate 

continuously without lubrication. 

Inspect the blower fans periodically 

for dirt on the blades, and remove 

it by gently brushing the blades or 

using a vacuum cleaner.

6.

 Clean the grilles and inspect the 

ductwork. Clean the grilles when 

they are dusty. At least once a year, 

visually inspect the ductwork leading 

to and from the HRV. Damaged ducts 

can lead to condensation problems, 

including wet insulation, water on 

the floor and, ice build-up. If the 

insulation itself is damaged.

7

. Arrange for an annual servicing.  

Your HRV/ERV should undergo 

annual general servicing by a 

certified contractor and who is 

familiar with your HRV. If possible, 

have your furnace and HRV serviced 

at the same time; this will result in 

less inconvenience and cost than 

two separate visits. 

QUESTION / ITEM 

DIAGNOSIS / SOLUTION

• HRV/ERV not running 

•   Verify breaker in main electrical panel

 

•  Verify the HRV or ERV is in the ON position

 

•  Verify the all wall controls switch on the HRV or ERV are activated to supply power to the unit

 

•  Unplug HRV or ERV verify if the controller is wired correctly to the connection box on the side of the unit

 

•  Verify main outlet polarization

• Air is too dry 

•   Increase the humidity level on the controller (Turn towards 60%)

 

•  Reduce continuous airflow rate

 

•  Switch ventilation mode from continuous to intermittent

 

•  Humidifier recommended if heating source is a forced air system

• Air too humid 

•  Suggest continuous operation of HRV or ERV

 

•  Reduce humidity level on dehumidistat (Turn towards 30%)

 

•  Increase continuous airflow rate

 

•  Insufficient ventilation, check capacity

 

•  Internal source of moisture, e.g. heating wood store in basement, possible leaks or poor insulation R-value and or  

 

  dryer is venting in basement

• Vibration or noise 

•  Verify that vibration mounting straps, hanging chains or wall bracket is used for hanging the units.

 

•  Verify that flexible duct connections are use between the HRV or ERV and the rigid duct.

 

•  Verify that the motors are operating and are not obscured by any debris

 

•  Insure motor moves freely with turning by hand.

• Cold air 

•  Misplaced supply outlets

 

•  Defrost no operating correctly

 

•  The HRV or ERV not properly balanced

 

•  High airflow on furnace continuous mode

 

•  Insure HRV or ERV is interlock when integrated with forced air system

• Contamination or Pollutants 

•  Insure proper clearance of ventilation hoods from source of contaminants 

• Condensation  

•  Verify that the HRV or ERV is level to insure proper drainage

 

•  Verify that the duct connection are fix and secured with screws to the HRV or ERV.

 

•  Verify the cold side duct connections are fully insulated and that vapor barrier is taped to insure a proper seal.

 

•  Look for signs of crushed section, failing duct straps, puncture vapor barrier, missing insulation.

 

•  Look for sign of water accumulation/leakage/dripping

 

•  Verify that the drain connection is not kinked; the “P” trap is not to close to unit or obscured with debris.

For proper orintation of louvers.

(Solace & PH ES Series only)

Summary of Contents for C3.14 HRV

Page 1: ...MODEL PE 7 15 PE 10 22 SS 3 80 Product of Greentek Greentek reserves the rights to modify a product without prior notice whether in price design color or codes in order to offer at all times quality products that are highly competitive Greentek 50 Kanalflakt Way Bouctouche NB E4S 3M5 1 888 724 5211 Fax 1 866 426 7430 www Greentek ca Item 463674 SEPT2018 ...

Page 2: ...ons 3 3 Description of your Ventilation System 4 4 Operation of the DuotrolTM System 5 5 Operation of your Wall Controls 6 11 6 Troubleshooting 12 7 Maintenance 12 8 Warranty 13 Before servicing or cleaning the HRV system always remove the power cord from the AC wall outlet To reduce the hazards of electric shock or fire do not perform any service to the HRV system other than those stated in the o...

Page 3: ...m the heat from the outgoing stale air and use this heat to temper the incoming fresh air which reduces the cost of effectively ventilating your home during winter NOTE Reverse process occurs in the summer months Fresh air Exhaust air Bathroom Control Forced air system HRV ERV Exhaust air hood Fresh air supply hood Exhaust and supply in the return Bathroom Control Forced air system HRV ERV Exhaust...

Page 4: ...nected to the drain pan and serves as drainage for the accumulation of water It is normal during summer months to find no condensation in drain pan or in drainage hose Automatic Defrost Sequence The defrost sequence is electronically controlled to measure the incoming outdoor air temperature the sequence is activated at 5 C 23 F and colder This system eliminates that the heat recovery or energy re...

Page 5: ...h speed until the level of humidity is below the set point The T 3 timer has completed its time period or once the cycles per hour has completed its cycle TIP During hot and humid days it is recommended that you put the system on INTERM mode This will reduce the amount of warm and humid fresh air coming inside the house NOTE The following controls EHC1 0 EHC1 5 RD 2 RD 3P RD 3D RD 4P RD 4D will ov...

Page 6: ...tion system will increase to high speed when a auxiliary control has been activated if installed Recommended for best indoor air quality ECO Friendly continuous ventilation energy savings mode The ventilation system operates at reduced rate of 30 in continuous and at a reduced rate of 15 during maximum ventilation speed RECIRC Recirculation ventilation mode The recirculation mode recycles already ...

Page 7: ...l of humidity is below the set point NOTE By turning the relative humidity Sensor Dial to the OFF position does not turn off the ventilation system It only deactivates the relative humidity sensor RD 2 MODELTM DEHUMIDISTAT FEATURES Dehumidistat to select the humidity level Range Control OFF NORMAL and REDUCED Green LED light on OVERRIDE Orange LED light on CONT INTERM Comes complete with Relative ...

Page 8: ...eated ambient air from a selected area and distributes throughout your home This enables the ventilation system to have an auxiliary air supply automatically during defrost sequence or when RECIRC mode is selected RD 3P MODELTM DEHUMIDISTAT PROFESSIONAL FEATURES Dehumidistat to select the humidity level Range Control OFF NORMAL and REDUCED Mode Control INTERM and CONT Green LED light on OVERRIDE O...

Page 9: ... SWITCH INTERM CONT INTERM When the selector switch is in the INTER position the ventilation system will only run on high speed when there is a request for ventilation At this time the unit will run on high speed until the level of humidity is below the set point The T 3 timer has completed its time period or once the cycles per hour has completed its cycle CONT Provides continuous ventilation The...

Page 10: ...er has completed its time period or once the cycles per hour has completed its cycle CONT Provides continuous ventilation The ventilation system will increase to high when there is a request from one of the wall controls Recommended for maximum indoor air quality RECIRC The recirculation mode recycles already heated ambient air from a selected area and distributes throughout your home This enables...

Page 11: ...ess button once this will deactivate T 3 push button time and your ventilation system will return to previous settings TIPS The T 3 model push button timer allows the homeowner control of the indoor humidity level in room were excess humidity is produced Ex Bathroom kitchen laundry room TIPS Always leave a small gap when closing curtains and blinds in the winter months this will allow proper circu...

Page 12: ...aged 7 Arrange for an annual servicing Your HRV ERV should undergo annual general servicing by a certified contractor and who is familiar with your HRV If possible have your furnace and HRV serviced at the same time this will result in less inconvenience and cost than two separate visits QUESTION ITEM DIAGNOSIS SOLUTION HRV ERV not running Verify breaker in main electrical panel Verify the HRV or ...

Page 13: ... Years PH7 15 PH7 15ES XPH1 5 PE7 15 PH10 22 PH10 22ES XPX2 0 PE10 22 XDH7 15 C3 14HRV SS3 80 HRV SS3 80ERV 2 Years RNC12 RNC1 0 RNC1 5 RNC2 0 RNC2 0ES LIMITED WARRANTY ON VENTILATION MOTORS Greentek warrants the ventilation motors against defects in material and workmanship within the models warranty period from the date of original installation Greentek will provide a new or remanufactured part ...

Page 14: ...50 Kanalflakt Way Bouctouche NB E4S 3M5 1 888 724 5211 Fax 1 866 426 7430 www greentek ca Item 463674 ...

Reviews: