2

Description

The Greenlee CM-1360, CM-1560, CMH-1000, and CMI-1000 Clamp Meters are hand-held testing devices 
with the following measurement capabilities:  AC and DC voltage, AC current, AC current AmpTip™, 
frequency, non-contact electric field (EF) detection, resistance, and capacitance. They also check diodes 
and verify continuity. These meters are designed to be placed on or removed from insulated or uninsulated 
conductors.

Additional functionality specific to each model includes:

Function

CMI-1000

CM-1560

CMH-1000

AC + DC Voltage

DC Current AmpTip™

DC + AC Current AmpTip™

DC Current

Flashlight

μDC Current

Temperature (K-style thermocouple)

Motor Rotation

Phase Rotation

Peak RMS Capture

5 ms Crest

Other capabilities include:

• Hold Mode to capture the present LCD value

• Record Minimum, Maximum, or Average Mode

• Zero Mode

• Intelligent Auto Power Off

• Automatic ranging

• Backlit LCD

Safety

Safety is essential in the use and maintenance of Greenlee tools and equipment. This instruction manual 
and any markings on the tool provide information for avoiding hazards and unsafe practices related to the 
use of this tool. Observe all of the safety information provided.

Purpose of This Manual

This instruction manual is intended to familiarize all personnel with the safe operation and maintenance 
procedures for the Greenlee CM-1360, CM-1560, CMH-1000, and CMI-1000 Clamp Meters.

Do not discard this product or throw away!  

All specifications are nominal and may change as design improvements occur. Greenlee Textron Inc. shall not be liable for 
damages resulting from misapplication or misuse of its products.

® Registered:  The color green for electrical test instruments is a registered trademark of Textron Innovations Inc.

AmpTip is a trademark of BTC.

KEEP THIS MANUAL

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for CM-1360

Page 1: ...n comprendre toutes les instructions et les informations sur la s curit de ce manuel avant d utiliser ou de proc der l entretien de cet outil Vor Bedienung oder Wartung dieses Messger tes bitte alle A...

Page 2: ...Mode Zero Mode Intelligent Auto Power Off Automatic ranging Backlit LCD Safety Safety is essential in the use and maintenance of Greenlee tools and equipment This instruction manual and any markings o...

Page 3: ...ged Clamp meter test leads or any other clamp accessory when used to make a measurement create a System The System is rated for CAT III 1000 V or CAT IV 600 V when using the test leads or accessories...

Page 4: ...generates electromagnetic interference can result in unstable or inaccurate readings Failure to observe these warnings could result in severe injury or death Electric shock hazard Do not change the me...

Page 5: ...ve common or ground input terminal L1 input for motor and phase rotation 8 Refer to explanation under Using the Features 9 Jaw lever 10 Keep hand or ngers below the dashed line during operation 11 Jaw...

Page 6: ...7 Relative zero function is enabled 18 Polarity indicator 19 VFD AC measurement with lter for accuracy on variable frequency drives 20 AC measurement is selected 21 AC DC measurement is selected 22 DC...

Page 7: ...rmal mode In zero mode the value on the LCD when the button is pressed becomes the offset As the input value changes the offset is subtracted from the actual value This modi ed value is shown on the L...

Page 8: ...ent categories III and IV These test leads include a cap that must be in place when used in measurement category III or IV applications Failure to observe this warning could result in severe injury or...

Page 9: ...RMS Value 100 100 100 100 Average Value 90 100 87 64 Crest Factor j 1 414 1 1 73 2 The crest factor is the ratio of the peak value to the RMS value it is represented by the Greek letter j AC DC True R...

Page 10: ...e selector to this symbol These icons appear on the display Connect the red lead to Connect the black lead to ALL MODELS Voltage AC V COM Voltage DC V COM Current AmpTip AC A N A N A Current AC A N A...

Page 11: ...400 0 Hz DC bias must be less than 50 of the Sine RMS value Accuracy of Frequency Range Display Range Accuracy xx xx 1 0 0 05 Hz xxx x 1 0 0 5 Hz Voltage Measurement V Hz EF VFD SELECT SELECT VFD AC V...

Page 12: ...for adjacent current carrying conductors is 0 02 A A AmpTip DC Current CM 1560 and CMI 1000 only Range Accuracy Range Accuracy 60 00 A 0 00 A to 3 99 A 1 5 0 15 A 4 00 A to 60 00 A 1 5 0 05 A Induced...

Page 13: ...st factor 1 4 1 at full scale and 2 8 1 at half scale Induced error for adjacent current carrying conductors is 0 05 A A For any measurement when the conductor is not positioned on the center of the j...

Page 14: ...Threshold Between 10 and 250 Response Time Approximately 32 ms Capacitance Measurement Capacitance Range Accuracy 200 0 F 2 0 0 4 F 2500 F 2 0 4 F For lm capacitors capacitors with negligible dielect...

Page 15: ...F 1 0 2 F Thermocouples supplied with meter meet standard JIS C 1602 1981 Electric Field A 10 mm 0 4 B SELECT A Non contact OR B Contact precision measurement Non contact EF Detection Typical Voltage...

Page 16: ...digits In an RF eld of 3V m all other modes and models not speci ed above Total Accuracy Speci ed Accuracy 20 digits Safety Double insulation per UL IEC EN61010 1 Ed 3 IEC EN61010 2 033 Ed 1 CAN CSA C...

Page 17: ...the main circuit breaker panels of a building s electrical system Measurement Category IV Primary supply level Overhead lines and other cable systems Some examples include cables meters transformers...

Page 18: ...to de veri caci n revise si las bater as est n bajas y es necesario reemplazarlas Garantie vie limit e La soci t Greenlee Textron Inc garantit l acheteur d origine de ces produits que ces derniers ne...

Reviews: