Greenlee Textron / Subsidiary of Textron Inc.
18
4455 Boeing Dr., Rockford, IL 61109-2988 815/397-7070
555BAT™ Battery-Powered Bender
Bending Instructions
90
°
Stubs
1.
Measure the length of the required stub.
2.
See the Minimum Stub Length formula on the
Deduct Table. The required stub must be equal to
or longer than the Minimum Stub Length.
3.
Measure and mark the stub length on the conduit.
This is Mark 1. Subtract the Deduct from this mark
and make a new mark. This is Mark 2.
4.
Align Mark 2 with the front edge of the hook and
bend the conduit.
Note:
When the operator presses “UNLOAD”,
the conduit may spring back a few degrees.
Compensate by overbending as shown in
the Scale Reading Table.
Deduct Table
RIGID
EMT
15
°
30
°
45
°
60
°
90
°
15
°
30
°
45
°
60
°
90
°
1/2
18-3/4
35
50
66-1/4 96-1/4 16-1/4 32-1/2 47-1/2 63-3/4
95
3/4
17-1/2 32-1/2 47-1/2 63-3/4
95
17-1/2 33-3/4 48-3/4 63-3/4
95
1
17-1/2 33-3/4 48-3/4
65
95
17-1/2 32-1/2 48-3/4
65
95
1-1/4 18-3/4 33-3/4 48-3/4 63-3/4
95
17-1/2 33-3/4 48-3/4
65
95
1-1/2 18-3/4 33-3/4 48-3/4
65
95
16-1/4 31-1/4 46-1/4 61-1/4 92-1/2
2
20
35
48-3/4 63-3/4 96-1/4 17-1/2 33-3/4 48-3/4 63-3/4
95
IMC
PVC Coated
15
°
30
°
45
°
60
°
90
°
15
°
30
°
45
°
60
°
90
°
1/2
20
36-1/4 51-1/4 67-1/2 98-3/4 17-1/2 33-3/4 48-3/4
65
95
3/4
20
36-1/4 51-1/4 67-1/2 97-1/2 17-1/2 33-3/4 48-3/4 63-3/4
95
1
21-1/4 36-1/4 51-1/4 66-1/4 97-1/2 17-1/2 32-1/2 47-1/2 63-3/4
95
1-1/4 18-3/4 33-3/4
50
65
96-1/4 18-3/4 33-3/4
50
65
95
1-1/2 17-1/2 33-3/4 48-3/4 63-3/4
95
18-3/4 33-3/4 48-3/4
65
95
2
20
35
50
65
96-1/4
20
35
48-3/4 63-3/4 96-1/4
Figures are approximate
Scale Reading Table
STUB LENGTH
DEDUCT
BENDING
MARK 1
STUB
LENGTH
MARK
STUB LENGTH
BENDING
MARK 1
STUB
LENGTH
MARK
SIZE
SIZE
SIZE
1/2
3/4
1
1-1/4
1-1/2
2
RIGID/PVC
7-1/2
9
11
14
14-1/4
16-1/8
DEDUCT
EMT
7
8-7/8
10-3/4
13-1/8
13-7/8
15-3/8
IMC
7-1/2
9
11
14
13-3/4
15-1/4
MINIMUM STUB LENGTH = DEDUCT PLUS 2 INCHES