background image

16

Model MSCF Modular Small Cabinet Fan

®

Every Three (3) Months

Filters -

 The filter in the unit should be inspected 

at least every three (3) months. Depending on the 
environment, filters could require changing or cleaning 
more or less often. The filters can be slid out of the 
coil connection side of the unit.
If washable filters are installed, they can be washed in 
warm soapy water. An adhesive spray can be applied 
to increase filter efficiency.
If disposable filters are installed, check by holding up 
to a light source. If light cannot pass through the filter, 
it should be replaced. Replacement filters should be 
of the same manufacturer and size. When reinstalling 
filters, be sure to install with the airflow in the correct 
direction indicated on the filter. 

Yearly

Bearings —

 Most bearings are permanently 

lubricated and require no further lubrication under 
normal use. Normal use being considered -20ºF to 
120ºF and in a relatively clean environment. Some 
bearings are re-lubricatable and will need to be re-
greased depending on fan use. Check your bearings 
for grease fittings to find out what type of bearing 
you have. If your fan is not being operated under 
normal use, bearings should be checked monthly for 
lubrication.

Motors —

 Motor maintenance is generally limited to 

cleaning and lubrication (where applicable). Cleaning 
should be limited to the exterior surfaces only. 
Removing dust and grease buildup on motor housing 
assures proper motor cooling. Greasing of motors 
is intended only when grease fittings are provided. 
Many fractional motors are permanently lubricated 
and require no further lubrication. Motors supplied 
with grease fittings should be greased in accordance 
with manufacturer’s recommendations. When motor 
temperature does not exceed 104ºF (40ºC), the grease 
should be replaced after 2000 hours of running time 
as a general rule.

Wheels —

 Wheels require very little attention when 

moving clean air. Occasionally, oil and dust may 
accumulate on the wheel causing imbalance. When 
this occurs the wheel and housing should be cleaned 
to assure smooth and safe operation. Inspect fan 
impeller and housing for fatigue, corrosion or wear.
Routinely check all fasteners, set screws and locking 
collars on the fan, bearing, drive, motor base and 
accessories for tightness.

Fan Maintenance

Belt Span

Deflection = 

Belt Span

64

Clockwise

CORRECT

WRONG

WRONG

WRONG

NOTE:  For motors of 1 hp or less a 

smaller sliding base bracket 

is used to attach to blower.

Greenheck recommends these procedures to ensure 
trouble-free operation of this unit. It is especially 
important to maintain heater units for clean and 
efficient operation. Most unit failures can be attributed 
to poor setup or poor maintenance.
A record of maintenance performed on this unit 
should be kept. This information will provide essential 
information if problems are encountered. A section at 
the back of this manual is provided for recording the 
unit’s maintenance history.

Two Weeks after Start-Up

Belts -

 Belts tend to stretch after a period of 

time. They should be 
periodically checked 
for wear and tightness. 
Approximately 3/8 inch 
of deflection per ft. 
of span between 
sheaves is standard for 
belt tightness. When 
replacing belts, use the 
same type as supplied 
with the unit. Matched 
belts should always be 
used on units with multi-groove pulleys.
If adjustments are made, it is very important to check 
the pulleys for proper alignment. Misaligned pulleys 
lead to excessive belt wear, vibration, noise and 
power loss.

Replacement of belts can be accomplished by 
loosening the motor to the point where the belts 
can be removed by hand. Do not force belts on or 
off as this may cause breakage of cords leading to 
premature belt failure. Belts should be adjusted as 
above.

CAUTION

When performing any maintenance on this unit, 
be certain the power is disconnected and cannot 
be accidentally turned on. The control center 
disconnect can be locked in the off position.

C

lo

c

k

w

is

e

Belt Span

Deflection = Belt Span

64

G

CORRECT

WRONG

WRONG

WRONG

Belt Alignment

Summary of Contents for MSCF-BI

Page 1: ...ation and Maintenance Manual Please read and save these instructions Read carefully before attempting to assemble install operate or maintain the product described Protect yourself and others by obser...

Page 2: ...are accounted for by referencing the bill of lading to ensure all items were received Inspect each crate for shipping damage before accepting delivery Notify the carrier if any damage is noticed The c...

Page 3: ...Electric Heater 15 Maintenance Fan 16 Coil 16 Drain Pan 16 Reference Start Up Documentation 17 Maintenance Log 18 19 Warranty Backcover Unit Layout 1 Fan and Cabinet Section 2 Cooling Section Chilled...

Page 4: ...3 0 inch 3 8 16 Spinlock Nut Two required per assembly 3 8 16 Spinlock Nut Two required per assembly HANGING ASSEMBLY BASE ASSEMBLY Mounting Instructions Greenheck s Modular Small Cabinet Fan MSCF sho...

Page 5: ...4 Row HW Steam 15 6 75 18 5 18 5 6 75 6 75 18 5 6 75 9 5 18 5 19 38 2 5 3 5 43 20 6 75 18 5 18 5 6 75 6 75 18 5 6 75 9 5 18 5 19 38 2 5 3 5 43 25 6 75 21 18 5 6 75 6 75 21 6 75 9 5 18 5 23 38 2 5 3 5...

Page 6: ...ertical Quantity Face Area Sloped Quantity Face Area 15 9x18 2 1 8 12x12 1 2 5 12x24 1 20 12x12 1 2 5 16x16 1 3 4 12x24 1 16x20 1 25 14x18 2 3 0 16x20 2 3 8 30 16x16 1 3 4 12x24 1 5 3 16x20 1 24x24 1...

Page 7: ...15 50 9 38 3 188 1 375 4 0 26 0 85 8 6 62 12 75 9 38 3 188 1 375 4 0 26 0 All dimensions are in inches NOTE With airflow from left to right the fluid enters the coil from the bottom connection Inlet...

Page 8: ...2 50 24 5 21 0 10 12 14 1 38 1 63 65 6 7 50 24 5 26 0 10 12 14 1 38 1 63 85 8 6 62 24 5 26 0 10 12 14 1 38 1 63 All dimensions are in inches Unit Size Face Area A B C L M N P 4 Row 6 Row 8 Row All Al...

Page 9: ...should be capped off cap Unit Size Face Area A B C D E F G 4 Row 6 8 Row 4 Row 6 Row 8 Row 30 3 2 38 24 5 18 5 9 25 11 0 7 88 8 50 8 5 7 00 12 0 45 4 5 50 24 5 18 5 9 25 11 0 7 88 8 50 8 5 7 00 12 5 5...

Page 10: ...rage and Fan RPM All access doors must be installed Measure and record the input voltage and motor amperage s To measure the fan RPM the blower door will need to be removed Minimize measurement time b...

Page 11: ...ductwork Repair Elbows or other obstructions may restrict fan outlet Correct or improve ductwork Belt slippage Adjust belt tension Unit running backwards Correct as shown in System Start Up section S...

Page 12: ...independently of the coils Undue stress should not be applied at the connection to coil headers 2 The condensate drain pipe should be sized adequately to ensure the condensate drains properly See Drai...

Page 13: ...are recommended for low pressure steam On high pressure systems bucket traps are normally recommended The thermostatic traps should be used only for air venting 3 Bucket traps are recommended for use...

Page 14: ...he requirements and practices described below are based on the National Electric Code NEC and The Space Heating Standard of the Underwriters Laboratories Inc UL Although UL requirements are uniform th...

Page 15: ...with the thermostat set to 70 F the heater will be off with a temperature sensing above 70 F As the temperature varies the steps turn on and off to hold the setpoint discharge temperature The colder...

Page 16: ...n air Occasionally oil and dust may accumulate on the wheel causing imbalance When this occurs the wheel and housing should be cleaned to assure smooth and safe operation Inspect fan impeller and hous...

Page 17: ...rated enough to prevent freeze up NOTE Carefully read instructions for mixing antifreeze solution used Some products will have a higher freezing point in their natural state than when mixed with water...

Page 18: ...___________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _________________...

Page 19: ...___________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _________________...

Page 20: ...or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Phone 715 359 6171 Fax 715 355 2399 E mail gfcinfo g...

Reviews: